Scenario Description - Huawei FusionModule2000 Installation Manual

Smart modular data center 2000 mmhigh cabinets, dual-row aisle containment, 208 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Figure 2-1
is an integrated UPS.
smart module.
The floor plan and exterior diagrams only indicate the relative positions of components.
For the detailed installation position, see the engineering layout diagram and actual
objects.
The PDC in smart module A is an integrated UPS, with batteries deployed inside the aisle
containment.
The PDC in smart module B is an integrated PDC or precision PDC, with batteries and
UPS deployed outside the aisle containment.
The PDC in smart module A (with batteries deployed outside) is an integrated UPS, with
batteries deployed outside the aisle containment.
It is recommended that two air conditioners with the heating and humidification functions
be installed for the standard configuration. In the dual-row aisle containment, the two air
conditioners should be placed at both ends of the aisle. If more than two air conditioners
with the heating and humidification functions are to be configured, distribute them evenly
in the aisle depending on the actual condition.
To attach labels subsequently, name the two rows of cabinets row A and row B respectively. Facing the
end door (PDC side), the left row is row A, and the right row is row B, as shown in
Issue 01 (2017-07-30)
2
shows the floor plan of the smart module A dual-row aisle containment. The PDC
Figure 2-2
shows the exterior of the dual-row aisle containment of the
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.

Scenario Description

2 Scenario Description
Figure
2-1.
16