Pipe Support - Huawei FusionModule2000 Installation Manual

Smart modular data center 2000 mmhigh cabinets, dual-row aisle containment, 208 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Figure 3-27 Connecting a drainpipe
(1) Rigid pipe: 1/2-inch BSPT, external thread, made of PP-R,
C-PVC, or other materials
(3) Hose: inner diameter of 14 mm, made of EPDM or other
materials
(5) Rigid pipe conversion adapter: 5/8-inch outer diameter,
adapting for 1/2-inch BSPP internal thread connection

3.2.6 Pipe Support

Figure 3-28
appearance depends on site situations.
Figure 3-28 Pipe support (unit: mm)
Issue 01 (2017-07-30)
Components inside the dashed-line boxes are ports on the equipment. Components 2, 4, and 5 are
mandatory. Other components are subject to engineering procurement.
shows a support for refrigerant pipes and water pipes. The specific support
U-shaped pipe clamp height H = Pipe diameter (including the thermal insulation foam) – 5 mm. Pipe
supports are not configured by Huawei.
Stainless steel 304 is recommended for pipe supports and pipe clamps.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
(2) Hose clamp
(4) Hose delivered
with the fittings
37