Huawei FusionModule5000 Product Description

Huawei FusionModule5000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

Quick Links

FusionModule5000 Smart Modular Data Center
V100R001
Product Description
Issue
01-(20170227)
Date
2017-02-27
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionModule5000

  • Page 1 FusionModule5000 Smart Modular Data Center V100R001 Product Description Issue 01-(20170227) Date 2017-02-27 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) About This Document Purpose This document describes the smart modular data center (smart module for short) as well as its application scenarios and system architecture, providing the systemic information about the smart module.
  • Page 4 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Symbol Description Calls attention to important information, best practices and tips. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration.
  • Page 5: Table Of Contents

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Contents About This Document ....................... ii 1 Overview ........................... 1 1.1 Product Model ............................... 1 1.2 Positioning ................................1 1.3 Features................................. 1 2 Typical Configurations ......................4 2.1 Typical Application Scenarios ..........................4 2.2 Typical Configurations............................
  • Page 6 FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.3 Cooling System ..............................52 3.3.1 System Description ............................53 3.3.2 NetCol5000-C 30 kW ............................53 3.3.2.1 Components..............................54 3.3.2.1.1 Cooling Components............................54 3.3.2.1.2 Controller ..............................55 3.3.2.1.3 Monitoring System............................56 3.3.2.2 Working Conditions ............................56 3.3.2.3 Technical Specifications ..........................58 3.3.2.4 Performance Curves ............................61...
  • Page 7 FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.8.2 Cable Routes for the Dual-Row Aisle Containment Scenario (New Main Way) ..........111 3.8.3 Cables ................................113 A Acronyms and Abbreviations .................... 114...
  • Page 8: Overview

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Overview 1.1 Product Model Table 1-1 shows the model of the smart module. Table 1-2 describes the model naming conventions. Table 1-1 Smart module model Fusion 5000 Module Table 1-2 Model naming conventions...
  • Page 9 FusionModule5000 Smart Modular Data Center Product Description (ECC800) flexible deployment, and excellent monitoring. It is a new-generation smart modular data center solution. Integration ⚫ The smart module integrates a cabinet system, power supply and distribution system, cooling system, facility management system, surge protection and grounding system, fire extinguishing system, and integrated cabling system.
  • Page 10 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Fast and Flexible Deployment ⚫ The integrated design supports relocation of communications equipment with offices. ⚫ Single-row cabinets or dual-row cabinets are deployed based on the equipment room size, power consumption of a single cabinet, and expansion requirements.
  • Page 11: Typical Configurations

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Typical Configurations 2.1 Typical Application Scenarios Based on the product layout, there are three types of architecture: smart module A (with the battery cabinet in the aisle containment), smart module A (without the battery cabinet in the aisle containment) and smart module B.
  • Page 12: Configurations For The Single-Row 1200 Mm Wide Aisle Containment

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 2.2.1 Configurations for the Single-Row 1200 mm Wide Aisle Containment Figure 2-1 Single-row aisle containment (power supply and distribution cabinet) Figure 2-2 Single-row aisle containment (new main way)
  • Page 13 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 2-3 Floor plan of the single-row 1200 mm wide aisle containment (power supply and distribution cabinet) The PDC refers to the precision PDC or integrated UPS cabinet. Table 2-1 lists the key technical specifications of the single-row 1200 mm wide aisle containment.
  • Page 14: Configurations For The Dual-Row 1200 Mm Wide Aisle Containment

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 2.2.2 Configurations for the Dual-Row 1200 mm Wide Aisle Containment Figure 2-4 Dual-row aisle containment (power supply and distribution cabinet) Figure 2-5 Dual-row aisle containment (new main way)
  • Page 15 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 2-6 Floor plan of the dual-row 1200 mm wide aisle containment (power supply and distribution cabinet) The PDC refers to the precision PDC or integrated UPS cabinet. Table 2-2 lists the key technical specifications of the dual-row 1200 mm wide aisle containment.
  • Page 16: System Architecture

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) System Architecture 3.1 System Architecture 3.1.1 Components of the Single-Row 1200 mm Wide Aisle Containment Overview The single-row 1200 mm wide aisle containment can be a cold or hot aisle containment that...
  • Page 17: Components Of The Dual-Row 1200 Mm Wide Aisle Containment

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) (4) Cable trough (5) Smart ETH gateway (6) Cabinet (7) Alarm beacon (8) Pad (9) Access control device Figure 3-2 Components of the single-row 1200 mm wide cold aisle containment (new main way)
  • Page 18 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-3 Components of the dual-row 1200 mm wide cold aisle containment (power supply and distribution cabinet) (1) End door (2) Flat or rotating skylight (3) Control skylight (4) Cable trough (5) Smart ETH gateway...
  • Page 19: Cabinet

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) (4) Power distribution unit (5) Busbar trunking unit (6) Flat or rotating skylight (7) Cable trough (8) Cabinet (9) Pad (10) Access control device (11) End door 3.1.3 IT Cabinet IT cabinets of the Smart Module comply with the International Electrotechnical Commission (IEC) 60297-1 standard, provide stable installation space for servers in the Smart Module, and ensure secure server running.
  • Page 20 FusionModule5000 Smart Modular Data Center Product Description (ECC800) ⚫ Static load: 1500 kg Table 3-1 Cabinet technical specifications Item Specifications Dimensions (H x W ⚫ 2000 mm x 600 mm x 1100 mm x D) ⚫ 2000 mm x 600 mm x 1200 mm ⚫...
  • Page 21: Network Cabinet

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Protection level IP20 3.1.4 Network Cabinet The network cabinet provides space for integrated cabling and cable management interface for the data center. For the network cabinet exterior, refer to the IT cabinet exterior. Table 3-2 lists the technical specifications of the network cabinet.
  • Page 22: Skylight

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Weight of an empty ⚫ The weight of a 2000 mm x 600 mm x 1200 mm cabinet cabinet is 128 kg. ⚫ The weight of a 2000 mm x 800 mm x 1200 mm cabinet is 153 kg.
  • Page 23 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Applicable Cabinet Name Dimensions (H x W x D) Dimensions (H x W x D) 300 mm wide 341 mm x 305 mm x 1334 mm ⚫ 2000 mm x 300 mm x 1200 flat skylight ⚫...
  • Page 24 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-7 800 mm wide control skylight (1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel Figure 3-8 600 mm wide flat or rotating skylight (1) Magnetic lock fixing base...
  • Page 25: End Doors For Aisles

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-9 800 mm wide flat or rotating skylight (1) Magnetic lock fixing base (2) Skylight connective plate (3) Flat skylight panel A rotating skylight is designed with an eccentric structure. When the trigger is activated, a rotating skylight falls under gravity.
  • Page 26: Cable Trough

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) The dimensions (H x W x D) of a sliding door are as follows. For a 2000 mm high cabinet, the dimensions of a sliding door are 2300 mm x 1400 mm x 54 For a 2200 mm high cabinet, the dimensions of a sliding door are 2500 mm x 1400 mm x 54 Sliding doors can be opened only sideways, and therefore may involve risks in the case of a fire.
  • Page 27: Optional) Adaptive Frame

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-12 300 mm wide cable trough (1) Bracket (2) Pallet (3) Baffle Figure 3-13 600/800mm wide cable trough (1) Bracket (2) Pallet (3) Baffle (4) Position for installing a smart ETH gateway 3.1.8 (Optional) Adaptive Frame...
  • Page 28: Optional) Base

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Width Depth Height Component Remarks (mm) (mm) (mm) PDC top frame 1200 300 mm air conditioner 1100 2000 Adapt to 1200 mm adaptive frame or 1100 mm deep 1200 2000 cabinets. When...
  • Page 29: Power Supply And Distribution System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Type Dimensions Description 800 mm wide Width: 800 mm; height: 270 mm Used to support an 800 mm wide IT ≤ H ≤ 410 mm (adjustable); base cabinet and 800 mm wide network depth: 1000 mm, 1100 mm, or cabinet.
  • Page 30: Power Supply And Distribution System Of Smart Module A

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) ⚫ The power supply and distribution system allows lead-acid batteries to power off automatically in the case of fire. 3.2.1 Power Supply and Distribution System of Smart Module A N+1 System Power Distribution Diagram Figure 3-14 shows the power distribution diagram for the N+1 system.
  • Page 31 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-15 2N system power distribution diagram...
  • Page 32: Power Supply And Distribution System Of Smart Module B

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.2.2 Power Supply and Distribution System of Smart Module B N+1 System Power Distribution Diagram Figure 3-16 N+1 system power distribution diagram (precision PDC) Figure 3-17 N+1 system power distribution diagram (new main way)
  • Page 33 FusionModule5000 Smart Modular Data Center Product Description (ECC800) 2N System Power Distribution Diagram Figure 3-18 2N system power distribution diagram (precision PDC) Figure 3-19 2N system power distribution diagram (new main way)
  • Page 34: Integrated Ups Cabinet

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.2.3 Integrated UPS Cabinet The integrated UPS cabinet has the following features. ⚫ Uses a unified architecture, and provides reliable quality, comprehensive functions, and consistent appearance. ⚫ Integrates an ATS or MCCB and components for distributing power to IT equipment, air conditioners, lights, and UPSs.
  • Page 35 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Power distribution circuit 40 A/1P x 18 x 2; 63 A/1P x 6 x 2 breakers for IT equipment Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm...
  • Page 36 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Category Item Specifications Battery string sharing Battery strings are shared in the cabinet by default. There are no combined cabinets in the Smart Module. Charge voltage Equalized charging voltage: 2.35 V/cell; float charging voltage: 2.25 V/cell...
  • Page 37: Precision Pdc

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.2.4 Precision PDC The precision PDC provides the following features: ⚫ Modular design, facilitating capacity expansion and backup ⚫ Compatible with cabinets of low to high power density Figure 3-21 and Figure 3-21 show the precision PDC with a single input.
  • Page 38 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-22 Precision PDC with a single input (1) Indicators (2) MCCB input circuit breaker (3) SPD and SPD circuit breaker (4) Monitoring board 1 (5) Monitoring board 2 (6) Monitoring board 3...
  • Page 39 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-23 Precision PDC with two inputs (1) Input module (2) Output module 1 (3) Output module 2 (4) Output module 3...
  • Page 40 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-24 Precision PDC with two inputs (1) Indicator of route I (2) Indicator of route II (3) Input circuit breaker of route I (4) Input circuit breaker of route II (5) SPD and SPD circuit breaker of route I...
  • Page 41: New Main Way

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Technical Specifications Rated frequency (Hz) 50/60 Rated operating current (A) 400/250/160 Enclosure protection level IP20 Output switch Single-phase 40 A; maximum: 144 single-phase routes Surge protection level Level C Cable routing...
  • Page 42 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Feature Description Power saving: saves about 1600 kWh power each year in a typical scenario with 80 kW 50% loads. Safe, reliable, and flexible O&M Reliability: uses a foolproof structure with installation position marks and spacing measures.
  • Page 43: Battery Cabinet

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Technical Specifications Electromagnetic compatibility (EMC) Class B environment Cabling mode Routed in from the end Cable connection capacity ⚫ 160 A rated current: 4 x 70 mm + 1 x 35 mm ⚫...
  • Page 44 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-26 Battery cabinet components (1) BIB (2) CIM (3) Batteries (4) Circuit breaker Table 3-11 lists the technical specifications of a battery cabinet. Table 3-11 Battery cabinet technical specifications Parameter Specifications Dimensions (H x W x D) ⚫...
  • Page 45 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Parameter Specifications Door opening mode The front door is a single door, and the rear door is a double one. Weight 128 kg (excluding batteries) Protection level IP20 Table 3-12 lists the number of batteries with different capacity a single battery cabinet can house.
  • Page 46: Pdu2000

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Batte Cabinet Main Battery Cabinet Auxiliary Battery Cabinet Layer Capa (from city Top to Bottom) The first Ah/10 layer 0 Ah second layer The third layer The fourth layer 3.2.7 PDU2000 Figure 3-27 and Figure 3-28 show PDU2000s.
  • Page 47: Intelligent Battery Monitoring System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) PDU2000 Type PDU2000 Model PDU2000 Output Port PDU2000-32-1PH-20/2-B1 20 x C13 + 2 x C19 (full height) PDU2000-32-3PH-12/9-B2 12 x C13 + 9 x C19 (full height) 3.2.8 Intelligent Battery Monitoring System The intelligent battery monitoring system consists of the CIM (CIM01C2) and BIM (BIM01C3).
  • Page 48: Cim

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-30 CIM communications cable connecting to a smart ETH gateway 3.2.8.1 CIM CIM is a battery information collection module. It collects battery status data from the downstream BIM groups through wireless communication, and sends the data to the ECC, UPS, and the third-party network management system (NMS) through COM or PoE ports.
  • Page 49 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-31 CIM front view (1) –48 V 0.5 A port (power (3) COM_IN port (RS485 (2) PoE port input) communication input) (4) COM_OUT port (RS485 (5) DI and DO ports (6) HALL_1–HALL_8 current...
  • Page 50 FusionModule5000 Smart Modular Data Center Product Description (ECC800) (3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485 reset) communications address) (5) 12V 2A port (power input) Power Port Figure 3-33 Power port pins Table 3-16 12 V, 2 A port pin definitions...
  • Page 51 FusionModule5000 Smart Modular Data Center Product Description (ECC800) PoE Port Figure 3-34 PoE port pins Table 3-18 PoE port pin definitions Definition Description Supports power supply through the PoE port. The TX– terminal is an RJ45 terminal with an indicator.
  • Page 52 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-19 COM port pin definitions Signal Description RS485+ Two cascaded RS485 communication ports RS485– RS485+ RS485– DI and DO Ports Table 3-20 DI and DO port pin definitions Signal Initial Definition...
  • Page 53 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Current Monitoring Port Figure 3-36 Current monitoring port pins Table 3-21 Current monitoring port pin definitions Definition Description +12 V Detect the charge and discharge currents of four –12 V battery strings or eight battery routes.
  • Page 54 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-22 BCB_1–BCB_4 port pin definitions Signal Initial Definition Status Description Remarks Description Status Monitors ⚫ Grounded: BCB Disconnected The four whether the connected. BCBs can BCB box is separately ⚫ Disconnected:...
  • Page 55 FusionModule5000 Smart Modular Data Center Product Description (ECC800) BCB_IN BCB_OUT Status Initial Descrip Definition Signal Signal Description Status tion Description Description Signal output Monitors ⚫ Grounded: Discon port port for the whether the nected cascadin battery circuit cascaded battery breaker status...
  • Page 56 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicator Color Meaning Status Description Measure RF_Z Green Wireless Steady No network Requires no communication parameters exist. handling. status (A network is to be created.) Blinking A network is at super being created...
  • Page 57 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicator Color Meaning Status Description Measure Alarm indicator Steady The actual Check the value number of of BIM number, online devices is the BIM cable less than the connection, and value of BIM the BIM number.
  • Page 58: Bim

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Name Definition Function Default button Hold down the button Reset to the default IP address for more than 10 (192.168.0.10) seconds. 3.2.8.2 BIM The BIM is a battery monitoring module that monitors the voltages, internal resistances, and pole temperatures of batteries and supports 12 V power.
  • Page 59: Cooling System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Silk Indicator Color Status Description Screen Blinking at The networking succeeds. long intervals Alarm The BIM is not faulty. Steady on ⚫ The BIM is faulty. ⚫ Communication with the CIM times out.
  • Page 60: System Description

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.3.1 System Description The cooling system uses chilled water in-row precision air conditioners and an aisle containment for cooling. The in-row precision air conditioners and equipment cabinets form an aisle containment as shown in Figure 3-39 to separate hot air from cold air.
  • Page 61: Components

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-40 Appearance 3.3.2.1 Components The NetCol5000-C consists of cooling components, the controller, and monitoring system. 3.3.2.1.1 Cooling Components The NetCol5000-C consists of the chilled water valve, electronic commutation (EC) fan, heat exchanger, air filter, condensate pump (optional), deflector (optional), electric heater (optional), and electrode humidifier (optional).
  • Page 62: Controller

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) The drainage system uses dual floats and double water pumps, achieving higher reliability. ⚫ Deflector (optional) It controls the horizontal supply air flow direction. ⚫ Electric heater (optional) The positive temperature coefficient (PTC) heater automatically adjusts heating capacity and provides multiple protection mechanisms to ensure operating security and reliability.
  • Page 63: Monitoring System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Features ⚫ Provides a touchscreen with a compact interface. ⚫ Controls the NetCol5000-C precisely and responds quickly. ⚫ Uses a multi-level password protection mechanism to prevent misoperation. ⚫ Protects the NetCol5000-C from power failures and water leaks, ensuring system reliability.
  • Page 64 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Environment Requirements ≤ 95% RH Operating humidity Altitude 0 m to 1000 m. The cooling capacity is derated when the altitude is above 1000 m. For details, see Figure 3-43. –40°C to +70°C Storage temperature ≤...
  • Page 65: Technical Specifications

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-32 Water quality requirements Name Specifications Unit Hydrogenion 7–8.5 μS/cm Conductivity rate at 20°C 300–1250 (σ a: When σ is less than 300 μS/cm, the first vapor exhausting duration of the humidifier is long;...
  • Page 66 FusionModule5000 Smart Modular Data Center Product Description (ECC800) NetCol5000-C030H6B2010020 NetCol5000-C030H6B201002 Item External ⚫ 2000 mm x 300 mm x 1000 ⚫ 2000 mm x 300 mm x 1000 dimensions (H x W x D) ⚫ 2000 mm x 300 mm x 1200 ⚫...
  • Page 67 FusionModule5000 Smart Modular Data Center Product Description (ECC800) NetCol5000-C030H7B201E12 NetCol5000-C030H7B2010020 Item Configuration of a condensate pump Configuration of an ⚫ For a 1000 mm deep model: air deflector ⚫ For a 1100 mm deep model: ⚫ For a 1200 mm deep model:...
  • Page 68: Performance Curves

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) NetCol5000-C030H7A201E12 NetCol5000-C030H7A201002 Item Power system 208 V to 240 V, 1 Ph, 50 Hz/60 208 V to 240 V, 1 Ph, 50 Hz/60 208 V rated voltage tolerance: 208 V rated voltage tolerance: –10% to +6%, 220 V and 240 V...
  • Page 69 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Cooling Capacity Derating Coefficient Curve in Proportion to the Altitude Figure 3-43 Cooling capacity derating coefficient curve in proportion to the altitude When the altitude is within 1000 m, the cooling capacity deviation is in the tolerance range and can be ignored.
  • Page 70: Management System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.4 Management System Table 3-36 Management system configurations Function ECC800 WEB ECC800 App NetEco Work order management Energy efficiency management PUE statistics Capacity management Generating alarms for SNMP northbound equipment Monitoring data for...
  • Page 71: System Description

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Function ECC800 WEB ECC800 App NetEco Battery monitoring Optional Optional Optional Log recording Management range A single smart A single smart Multiple smart module module modules Configuration Mandatory Optional Optional principle 3.4.1 System Description The management system consists of the management software and other components.
  • Page 72: Server

    3.4.2 Server Tecal RH2288V2 Server The Tecal RH2288V2 rack server (RH2288V2 for short) of Huawei features large capacity and high performance and can meet customers' medium and long term requirements. It serves as the monitoring host of the NetEco and is responsible for data processing and analysis.
  • Page 73: Ecc800

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-47 RH2288V2 server The RH2288V2 has the following features: ⚫ It has powerful computing and storage capacity and scalability. ⚫ It can be flexibly configured with value-added components and has multiple functions.
  • Page 74 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-48 ECC800 controller (front view) (1) PSU (2) PSU (3) Status (4) 3G/4G indicator antenna port (5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW and LAN_1–LAN_2) input port...
  • Page 75 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Power input ⚫ Supports two AC inputs ⚫ Rated voltage; 200–240 V AC/100–120 V AC ⚫ rated frequency; 50 Hz/60 Hz ⚫ Input current; 6.7 A Power output ⚫ rated voltage: 53.5 V DC ⚫...
  • Page 76 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicators Table 3-39 describes the indicators on the ECC800 monitoring module. Table 3-39 Indicators on the ECC800 monitoring module Indicat Color Name Status Description Green Running status Steady on The power supply is normal, the...
  • Page 77 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Color Name Status Description Blinking at A network is set up, and node super short access is allowed (the indicator intervals blinks at 10 Hz, on for 0.05s and then off for 0.05s).
  • Page 78 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Colo Indicator Name Status Description Fault Steady on The converter locks out due to indicator output overvoltage. The converter delivers no output due to internal faults. The converter is working properly. Wireless Network Pairing (SW) and IP Address Reset (Default) Buttons Table 3-41 describes the wireless network pairing and IP address reset buttons.
  • Page 79: Lan Switch

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Button Function Operation Description Indicator Status Name Description WiFi pairing In non-WiFi pairing mode, press the ⚫ When the system button button for less than 1.2s to enter the enters the pairing WiFi pairing mode.
  • Page 80: Video System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-50 S5320 LAN switch Table 3-42 describes parameters of the S5320 LAN switch. Table 3-42 Parameters of the S5320 LAN switch Item Parameter Dimensions (H x W x D) 44.4 mm x 442 mm x 420 mm Maximum power consumption (fully 913 W (Power consumption: 173 W;...
  • Page 81 FusionModule5000 Smart Modular Data Center Product Description (ECC800) the ECC800 IP address. Therefore, the IPC6325 camera IP address should be reset before camera commissioning begins. The IPC6325-WD-VR network camera (IPC6325 camera for short) is a two-megapixel wide dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.
  • Page 82: Vcn500

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.4.5.2 VCN500 Figure 3-52 shows a VCN500. Figure 3-52 VCN500 Table 3-44 lists the performance indicators of a VCN500. Table 3-44 Performance indicators of a VCN500 Item Description Video input A single VCN500 connects to a maximum of 32 cameras and a maximum inbound bandwidth of 160 Mbit/s.
  • Page 83: Skylight Control System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Description Power parameters Single power supply only Maximum PSU power: 250 W AC power input voltage range: 100–240 V AC power frequency range: 50–60 Hz ≤ 20 kg Full configuration weight...
  • Page 84 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-53 Skylight actuator (1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor magnetic lock DO window open button DI input port input port output port input port (5) BLINK button...
  • Page 85 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications DO output One 12 V DC power output for controlling the skylight magnetic lock; driving six skylight magnetic locks simultaneously DI input One DI input port for connecting to the window open button BLINK ⚫...
  • Page 86: Access Control System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description RF_Z Gree Communication Steady on No network parameters exist, or a status indicator network is to be created. Blinking at A network is set up, and no node...
  • Page 87 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-54 Access actuator (1) 48 V power (2) PoE port (3) RS485 port (4) RS485 port COM1 port COM2 (5) Address DIP (6) Status (7) BLINK (8) WG_2 Wiegand interface switch...
  • Page 88 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications DO output One 12 V DC power output that controls magnetic locks, phoenix terminal DI input One DI input port for connecting to the door status switch RS485 serial Two RS485 ports (one route) with the default communications rate of...
  • Page 89 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description Blinking The indicator blinks at super short intervals for 0.5s (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s. The cycle lasts for 10s.
  • Page 90: Aisle Access Control

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.4.7.2 Aisle Access Control The aisle access control system applies to the aisle containment. It provides monitoring and data for devices and personnel moving into or out of the aisle containment. It can support the fingerprint and card reader with a password keyboard, fingerprint and card reader, and card reader with a password keyboard.
  • Page 91 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Operating status ⚫ Standby: The blue indicator is on, and the green indicator on the fingerprint acquisition position is steady on ⚫ Acquiring fingerprints: The red indicator on the fingerprint acquisition position is on ⚫...
  • Page 92 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Operating current Rated 300 mA±5% Supported card IC card Authorized storage A maximum of 3000 authorized users, a maximum of 6000 fingerprints Communication mode RS485 port, Wiegand port Operating status ⚫...
  • Page 93 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-54 Specifications of a card reader with a password keyboard Item Specifications Dimensions (L x W x H) 114mmx63mmx25mm Operating voltage Range: 10.8–13.2 V DC, rated voltage: 12 V DC Operating current...
  • Page 94: Optional) Cabinet Access Control System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) ⚫ The access control system consists of the access controller (for double doors), fingerprint reader with a password keyboard, magnetic lock, and exit button. ⚫ The emergency door release button can disconnect the power supply to the electronic lock to open the door in case of emergency.
  • Page 95: Optional) Water Sensor

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Mechanical Lock Figure 3-61 shows a mechanical lock. Figure 3-61 Mechanical lock Functions and features: ⚫ The cabinet door can be opened with only the key and without the password. ⚫ The cabinet door can be opened with only the password and without the key.
  • Page 96: Optional) Smoke Detector

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-62 Water sensor and water detection cable Table 3-56 Technical specifications of a water sensor Item Specifications Operating voltage 12 V DC (9–16 V DC) Output when no liquid exists CLOSED...
  • Page 97: Optional) Temperature Sensor

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-63 Smoke detector Table 3-57 Technical specifications of a smoke detector Item Specifications Operating voltage 9–16 V DC Quiescent current < 8 mA Alarm current < 35 mA Output mode Relay output...
  • Page 98: Multi-Functional Sensor

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-58 lists the temperature sensor specifications. Table 3-58 Temperature sensor specifications Item Specifications –20ºC to +70ºC Measurement range Measurement precision ±1ºC –10ºC to +55ºC Operating temperature Operating voltage 10–16 V DC –40ºC to +70ºC...
  • Page 99 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications PoE port One PoE port that complies with IEEE802.3AT RS485 port Reserved DI input One DI input port, 12 V DC power input BLINK button Wireless communication: ⚫ Press the button for less than 1s to start blinking.
  • Page 100: Rack Environment Unit

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description No system alarm is generated. RF_Z Gree Communication Steady on No network parameters exist, or a status indicator network is to be created. Blinking at A network is set up, and no node...
  • Page 101 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Specifications Table 3-61 lists the environment specifications for the rack environment unit. Table 3-61 Technical specifications for the rack environment unit Item Specifications Power input Phoenix terminal, with input voltage of 36–60 V DC...
  • Page 102: Smart Eth Gateway

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description Blinking The indicator blinks at super short intervals for 0.5s (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s. The cycle lasts for 10s.
  • Page 103 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications Power input PWR_IN D-type power input terminal, for power cascading, input voltage range: 45–55 V DC ⚫ Power output PWR_OUT D-type power output terminal, for power cascading, output voltage range: 45–55 V DC ⚫...
  • Page 104: Wifi Converter

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description Alarm indicator Steady on A system failure alarm is generated. No system alarm is generated. 3.4.14 WiFi Converter The WiFi converter is used in a modular data center to convert PoE signals into WiFi signals for communicating with devices such as the pad and mobile phone.
  • Page 105 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications WiFi function ⚫ 2.4 GHz frequency, two antennas, supporting eight STA connections, 50 m WiFi coverage (no blockage) ⚫ Support the WPS button PoE port One PoE port, complying with IEEE802.3AT, 25.5 W...
  • Page 106: Alarm Beacon

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description indicator Blinking WPS matching mode. If the matching fails, the WPS indicator turns off after blinking for 2 minutes. If the matching is successful, the WPS indicator turns off.
  • Page 107: Pad

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-68 Technical specifications of an alarm beacon Item Specifications RJ45 port, input voltage 9–16 V DC, operating current ≤ 400 Power input ≥ 100 ± 3 dB/30 cm Sound pressure ≥ 45 min...
  • Page 108: Cable Management

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Table 3-70lists PAD technical specifications. Table 3-70 PAD technical specifications Item Specifications Touchscreen 9.6-inch, 1280x800 IPS full view, IPS screen, and capacitive five-point touch Chip processor MSM8916, quad-core A53, 1.2 GHz integrated chip WLAN 802.11a/b/g/n@2.4GHz&5GHz...
  • Page 109 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-71 Cable manager Table 3-71 Cable manager specifications Dimensions (H x W x D) Weight Space Occupied 43.6 mm x 482.6 mm x 91 0.56 kg Cable Ring A cable ring is installed on a side post in the cabinet to secure vertically routed cables.
  • Page 110: Lighting System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Name Dimensions (H x W x D) Weight Standard cable ring 55 mm x 48 mm x 188.6 0.163 kg Small cable ring 55 mm x 48 mm x 44 mm 0.096 kg Cable Tray A cable tray is used for forward and backward cabling.
  • Page 111 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-74 shows an AC actuator. Figure 3-74 AC actuator (1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator (5) BLINK button (6) AI/DI dry (7) COM1–2 RS485...
  • Page 112 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Item Specifications BLINK ⚫ Press the button for less than 1 second to start blinking. button ⚫ Hold down the button for 1–5 seconds to search for a network and start networking.
  • Page 113: Aisle Lights

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Indicat Name Status Description Blinking at A network is set up, and node super short access is allowed (the indicator intervals blinks at 10 Hz, on for 0.05s and then off for 0.05s).
  • Page 114: Surge Protection And Grounding System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.7 Surge Protection and Grounding System The surge protection and grounding system of the Smart Module consists of the surge protection solution and grounding solution. 3.7.1 Surge Protection Solution Surge protection modules are installed in the integrated UPS cabinet and precision PDC.
  • Page 115 FusionModule5000 Smart Modular Data Center Product Description (ECC800) The new main way is grounded over the ground point on the general input unit. As shown in Figure 3-76 and Figure 3-77: Each cabinet in the smart module connects to the nearest ground grid using ground cables with the minimum cross-sectional area of 16 mm Use 100 x 0.3 copper foils or copper braids with a cross-sectional area of 25 mm...
  • Page 116: Integrated Cabling System

    FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-78 Equipotential cable connections for single-row cabinets In a dual-row aisle containment, two branch ground copper bars are used. The general ground copper bar is in the PDC, and a branch ground copper bar is in the first IT cabinet near the PDC.
  • Page 117 FusionModule5000 Smart Modular Data Center Product Description (ECC800) other end of the module, and the signal cables are routed through the control skylight located on the top of the network cabinet to the other end of the module. Figure 3-80shows how to route cables.
  • Page 118 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Figure 3-81 Diagram for routing cables between modules (1) Power cable (2) Signal cable (3) Optical fiber 3.8.2 Cable Routes for the Dual-Row Aisle Containment Scenario (New Main Way) Figure 3-82 shows how cables are routed in the dual-row aisle containment scenario when...
  • Page 119 FusionModule5000 Smart Modular Data Center Product Description (ECC800) ⚫ Ensure that strong-current cables and weak-current cables are at least 100 mm away from each other. ⚫ Connect the power cables from the general input unit side to the smart module.
  • Page 120 FusionModule5000 Smart Modular Data Center Product Description (ECC800) 3.8.3 Cables Power Cable The power cables include power cables to UPSs, battery cabinets, air conditioners, and PDU2000s. Ground Cable The ground cables include ground cables to PDU8000s, battery cabinets, and IT cabinets.
  • Page 121 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Acronyms and Abbreviations alternate current Auto Transformer Switch Battery Circuit Breaker Battery control I/O board Battery Interface Module BSPP British Standard Pipe Parallel Thread Controller Area Network Conformité Européenne Computational Fluid Dynamics...
  • Page 122 FusionModule5000 Smart Modular Data Center Product Description (ECC800) Fast Ethernet iBAT ibattery Integrated Circuit Internet Data Center Internet Technology Liquid Crystal Display Light Emitting Diode MTBF mean time between failures MTTR mean time to repair negative temperature coefficient Power Distribution Cabinet...
  • Page 123 FusionModule5000 Smart Modular Data Center Product Description (ECC800) SNMP Simple Network Management Protocol surge protective device Universal Series Bus uninterruptible power system Video Cloud Node WiFi Wireless Fidelity...

This manual is also suitable for:

V100r001

Table of Contents