FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
8.
Step 6 Connect the dehumidifier power cable.
1.
2.
3.
4.
5.
Step 7 Open the dehumidifier panel, start the dehumidifier, slowly pour water into the water channel
connected to the dehumidifier, and check that the water pump can drain water smoothly.
Step 8 Reinstall the dehumidifier panel, start the dehumidifier, and set the humidity for the
dehumidifier.
----End
A.6 (Optional) Connecting Cables to Industrial
Connectors
Figure A-36
cable connections depend on the industrial connector type and wiring port silk screen.
Figure A-36 Connecting cables to the industrial connector (three-core cable)
Issue 01 (2017-07-30)
Mix AB glue and apply it evenly where the dehumidifier drainpipe and the plug with
outer screw threads are connected, and keep the glued parts steady for 30 minutes to
solidify the glue.
Cut off the national standard three-pin plug of the power cable delivered with the
dehumidifier, and strip the power cable insulation layer for a proper length.
Strip the insulation layers of the brown and blue wires of cable 25030384 at both ends,
and wrap the yellow and green wires with insulation tape.
Crimp and connect the live and neutral wires of the dehumidifier power cable to the
brown and blue wires of cable 25030384 respectively using the conversion cord end
terminals delivered with the dehumidifier.
Crimp the other end of the brown wire using cord end terminal 14170096, and the other
end of the blue wire using OT terminal 14170014. Route the cable out of the cabinet top
to the PDC through the strong-current cable trough. Connect the brown wire to the 10 A
circuit breaker or lighting circuit breaker reserved in the PDC, and connect the blue wire
to the N bar in the PDC.
Crimp the PE wire of the dehumidifier power cable using the OT terminal (M6)
delivered with the dehumidifier, and connect the crimped terminal to a nearby ground
point in the IT cabinet.
to
Figure A-37
show only the cable connection methods. The industrial connector
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Appendix
242