FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Figure 1-7 Usage of marking-off templates
(A) Properly located cabinet
Aisle Check Tool
Aisle check tool dimension description:
When checking the height, ensure that the floor levelness meets engineering requirements
(floor levelness tolerance: 3 mm/2000 mm).
Issue 01 (2017-07-30)
Longer-side length: check whether the distance between the cabinet frames in two rows
of cabinets is 1284 mm.
Shorter-side length: check whether the distance between the doors in two rows of
cabinets is 1200 mm.
Height: check whether the lower edge of the cabinet frame is 44 mm above the floor.
Huawei Proprietary and Confidential