Huawei FusionModule2000 Product Description

Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

Quick Links

FusionModule2000 Smart Modular Data Center
V500R002
Product Description (380 V)
Issue
04
Date
2017-06-30
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionModule2000

  • Page 1 FusionModule2000 Smart Modular Data Center V500R002 Product Description (380 V) Issue Date 2017-06-30 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    FusionModule2000 Smart Modular Data Center Product Description (380 V) About This Document About This Document Purpose This document describes the smart modular data center (smart module for short) as well as its application scenarios and system architecture, providing the systemic information about the smart module.
  • Page 4 Added the descriptions about the base, precision PDC, and the L1/L2 function of the air conditioner. Issue 02 (2016-08-30) Changed the product name from IDS2000 to FusionModule2000. Issue 01 (2016-06-07) This issue is the first official release. Issue 04 (2017-06-30) Huawei Proprietary and Confidential Copyright ©...
  • Page 5: Table Of Contents

    FusionModule2000 Smart Modular Data Center Product Description (380 V) Contents Contents About This Document ......................ii 1 Overview ..........................1 1.1 Product Model ..................................1 1.2 Positioning ..................................... 1 1.3 Features....................................1 2 Typical Configurations ......................4 2.1 Typical Application Scenarios.............................. 4 2.2 Typical Configurations .................................
  • Page 6 FusionModule2000 Smart Modular Data Center Product Description (380 V) Contents 3.2.8.1 CIM....................................45 3.2.8.2 BIM....................................55 3.3 Cooling System ................................... 57 3.3.1 System Description ................................58 3.3.2 L1/L2 Linkage (iCooling Function) ..........................58 3.3.3 NetCol5000-A 25 kW ..............................59 3.3.3.1 Composition .................................. 59 3.3.3.1.1 Indoor Unit Components............................
  • Page 7 FusionModule2000 Smart Modular Data Center Product Description (380 V) Contents 3.4.13 Smart ETH Gateway..............................117 3.4.14 WiFi Converter ................................119 3.4.15 Alarm Beacon................................121 3.4.16 ETH Converter................................122 3.4.17 Pad ....................................124 3.5 Cable Management System ..............................125 3.6 Lighting System ................................127 3.6.1 AC Actuator..................................127 3.6.2 Aisle Light ..................................130...
  • Page 8: Overview

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 1 Overview Overview About This Chapter 1.1 Product Model 1.2 Positioning 1.3 Features 1.1 Product Model Table 1-1 Model naming conventions Model Category Definition FusionModule Product name Smart modular data center...
  • Page 9 FusionModule2000 Smart Modular Data Center Product Description (380 V) 1 Overview Integration  The smart module integrates a cabinet system, power supply and distribution system, cooling system, facility management system, surge protection and grounding system, auxiliary fire extinguishing system, and integrated cabling system. It provides an overall solution.
  • Page 10 FusionModule2000 Smart Modular Data Center Product Description (380 V) 1 Overview Fast and Flexible Deployment  The integrated design supports relocation of communications equipment with offices.  Single-row cabinets or dual-row cabinets are deployed based on the equipment room size, power consumption of a single cabinet, and expansion requirements.
  • Page 11: Typical Configurations

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 2 Typical Configurations Typical Configurations About This Chapter The FusionModule2000 is typically configured with the single-row or dual-row 1200 mm wide aisle containment. 2.1 Typical Application Scenarios 2.2 Typical Configurations 2.1 Typical Application Scenarios...
  • Page 12: Single-Row 1200 Mm Wide Aisle Containment

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 2 Typical Configurations 2.2.1 Single-Row 1200 mm Wide Aisle Containment Figure 2-1 Single-row aisle containment Figure 2-2 Floor plan of the single-row 1200 mm wide aisle containment The PDC refers to the integrated UPS cabinet, integrated PDC, or precision PDC.
  • Page 13: Dual-Row 1200 Mm Wide Aisle Containment

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 2 Typical Configurations Item Specifications Cooling NetCol5000-A 25 kW air cooled in-row precision air conditioner (300 mm wide); NetCol5000-A 25 kW & 35 kW air cooled in-row precision air conditioner (600 mm wide)
  • Page 14 FusionModule2000 Smart Modular Data Center Product Description (380 V) 2 Typical Configurations Figure 2-4 Floor plan of the dual-row 1200 mm wide aisle containment The PDC refers to the precision PDC, integrated UPS cabinet, or integrated PDC. Table 2-2 Key technical specifications...
  • Page 15: System Architecture

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture System Architecture About This Chapter 3.1 System Architecture 3.2 Power Supply and Distribution System 3.3 Cooling System 3.4 Management System 3.6 Lighting System 3.7 Surge Protection and Grounding System 3.8 Integrated Cabling System...
  • Page 16: Components Of The Dual-Row 1200 Mm Wide Aisle Containment

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-1 Components of the single-row 1200 mm wide cold aisle containment (1) End door (2) Flat or rotating skylight (3) Control skylight (4) Cable trough (5) Smart ETH gateway...
  • Page 17: Cabinet

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-2 Components of the dual-row 1200 mm wide cold aisle containment (1) End door (2) Flat or rotating skylight (3) Control skylight (4) Cable trough (5) Smart ETH gateway...
  • Page 18 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-3 IT cabinet An IT cabinet has the following features:  The ventilation rate of the front and rear doors is greater than or equal to 70%.
  • Page 19: Network Cabinet

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications Material High-intensity class A carbon cold rolled steel plate and zinc-coated steel plate Air channel Front and rear air channels Installation space  A 2000 mm high cabinet provides 42 U available space.
  • Page 20: Skylight

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications Color Black Material High-intensity class A carbon cold rolled steel plate and zinc-coated steel plate Air channel Front and rear air channels  Installation space A 2000 mm high cabinet provides 42 U available space.
  • Page 21 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Name Dimensions (H x W x D) Applicable Cabinet Dimensions (H x W x D)  2200 mm x 800 mm x 1200 300 mm wide 341 mm x 305 mm x 1334 mm ...
  • Page 22 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-5 Control skylight (1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel Figure 3-6 600 mm wide flat or rotating skylight (1) Magnetic lock fixing base...
  • Page 23: End Doors For Aisles

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-7 800 mm wide flat or rotating skylight (1) Magnetic lock fixing base (2) Skylight connective plate (3) Rotating skylight panel A rotating skylight is designed with an eccentric structure. When an electronic lock is triggered, the skylight rotates and then opens.
  • Page 24: Cable Trough

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture For a 2000 mm high cabinet, the dimensions of a sliding door are 2300 mm x 1400 mm x 54 For a 2200 mm high cabinet, the dimensions of a sliding door are 2500 mm x 1400 mm x 54 Sliding doors can be opened only sideways, and therefore may involve risks during fire extinguishing system acceptance.
  • Page 25: Optional) Cable Tray

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-10 300 mm cable trough (1) Bracket (2) Pallet (3) Baffle Figure 3-11 600 mm or 800 mm cable trough (1) Bracket (2) Pallet (3) Baffle (4) Position for a smart ETH gateway 3.1.8 (Optional) Cable Tray...
  • Page 26: Optional) Adaptive Frame

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-12 Cable tray (1) Cable ladder support (2) Cable ladder 3.1.9 (Optional) Adaptive Frame To meet requirements for cabinet height and depth in different scenarios, tail frames, top frames, and adaptive frames can be installed to ensure that all cabinets in the smart module have the same height and depth and that the two rows of cabinets have the same length.
  • Page 27: Optional) Base

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.1.10 (Optional) Base Adjustable Bases The widths of adjustable bases for a smart module include 300 mm, 600 mm, and 800 mm. The minimum adjustment range is 1 mm.
  • Page 28: Scenario With Columns

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.1.11 Scenario with Columns The smart module supports the scenario with columns if the following conditions are met:  The dimensions of a column in the data center are not greater than 1100 mm x 1100 mm.
  • Page 29 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-14 Adjustable skylight components (1) Skylight connective plates (2) Polycarbonate (PC) plate fasteners (3) L-shaped mounting bracket (4) PC plate clip (5) PC plate supports (6) PC plate (7) Telescopic edges Install adjustable skylights based on site situations.
  • Page 30 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-16 Dual-row aisle containment with columns (A ≥ 800 mm and B ≥ 400 mm) Figure 3-17 Single-row aisle containment with columns (A < 800 mm and B ≥ 400 mm)
  • Page 31: Power Supply And Distribution System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-18 Single-row aisle containment with columns (A ≥ 800 mm and B ≥ 400 mm) 3.2 Power Supply and Distribution System Features  The smart module has an integrated and intelligent power supply and distribution system, and supports N+1 system or 2N system power distribution.
  • Page 32: Power Supply And Distribution System Of Smart Module A

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.2.1 Power Supply and Distribution System of Smart Module A N+1 Structure System Power Distribution Diagram Figure 3-19 N+1 system power distribution diagram Issue 04 (2017-06-30) Huawei Proprietary and Confidential...
  • Page 33 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 2N Structure System Power Distribution Diagram Figure 3-20 2N system power distribution diagram Issue 04 (2017-06-30) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Power Supply And Distribution System Of Smart Module B

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.2.2 Power Supply and Distribution System of Smart Module B Power Distribution Diagram for Air Conditioners with a Single Input Figure 3-21 Power distribution diagram for air conditioners with a single input...
  • Page 35 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Power Distribution Diagram for Air Conditioners with Dual MCCB Inputs Figure 3-22 Power distribution diagram for air conditioners with dual MCCB inputs Issue 04 (2017-06-30) Huawei Proprietary and Confidential...
  • Page 36 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Power Distribution Diagram for Air Conditioners with Dual ATS Inputs Figure 3-23 Power distribution diagram for air conditioners with dual ATS inputs Power Distribution Diagram for Precision PDCs with a Single Input...
  • Page 37: Integrated Ups Cabinet

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Power Distribution Diagram for Precision PDCs with Dual Inputs Figure 3-25 Power distribution diagram for precision PDCs with dual inputs 3.2.3 Integrated UPS Cabinet The integrated UPS has the following features: ...
  • Page 38 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-26 Integrated UPS cabinet Table 3-7 lists the configurations of an integrated UPS cabinet. Table 3-7 Structural specifications of an integrated UPS cabinet Configuration Scenario 1 Scenario 2...
  • Page 39 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture circuit breakers for 63 A/1P x 6 x 2 63 A/1P x 6 IT equipment Dimensions (H x 2000 mm x 600 mm x 1100 mm W x D)
  • Page 40 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Category Item Specifications 125% < load ≤ 150%: transfer to bypass  mode after 1 min Bypass overload capability: Load ≤ 135%: run continuously at 30°C or ...
  • Page 41: Integrated Pdc

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture (Optional) ATS Table 3-9 lists the ATS specifications. Table 3-9 ATS specifications Item Specifications Input voltage range 187–264 V AC (phase voltage) Input frequency 40–70 Hz range 3.2.4 Integrated PDC The integrated PDC has the following features.
  • Page 42: Precision Pdc

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-10lists the configurations of an integrated PDC. Table 3-10 Integrated PDC configurations Configuration Air-cooled 1 Air-cooled 2 Air-cooled 3 Air conditioner input Single input Dual inputs ATS input...
  • Page 43 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-28 Precision PDC with a single input (1) Input module (2) Output module 1 (3) Output module 2 (4) Output module 3 Issue 04 (2017-06-30) Huawei Proprietary and Confidential...
  • Page 44 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-29 Precision PDC with a single input (1) Indicators (2) Input molded case circuit breaker (MCCB) (3) SPD and SPD circuit breaker (4) Monitoring board 1 (5) Monitoring board 2...
  • Page 45 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-30 Precision PDC with two inputs (1) Input module (2) Output module 1 (3) Output module 2 (4) Output module 3 Issue 04 (2017-06-30) Huawei Proprietary and Confidential...
  • Page 46 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-31 Precision PDC with two inputs (1) Indicator of route I (2) Indicator of route II (3) Input circuit breaker of route I (4) Input circuit breaker of route II...
  • Page 47: Battery Cabinet

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Technical Specifications Rated frequency (Hz) 50/60 Rated operating current (A) 400/250/160 Enclosure protection level IP20 Output switch 40 A single-phase, maximum 144 routes (single-phase) Surge protection level...
  • Page 48 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-33 Battery cabinet components (1) BIB (2) CIM (3) Batteries (4) Circuit breaker Table 3-12 lists the technical specifications of a battery cabinet. Table 3-12 Battery cabinet technical specifications...
  • Page 49 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications Door opening mode The front door is a single door, and the rear door is a double one. Weight 128 kg (excluding batteries) Protection level IP20 Table 3-13 lists the number of batteries with different capacity a single battery cabinet can house.
  • Page 50: Pdu2000

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-15 Configuration scenarios (The main battery cabinet and auxiliary battery cabinet are differentiated.) Batte Layer Main Battery Cabinet Auxiliary Battery Cabinet (from Speci Top to ficati Bottom)
  • Page 51: Intelligent Battery Monitoring System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture PDU2000 Type PDU2000 Model PDU2000 Output Port PDU2000-32-3PH-12/9-B1 12 x C13 + 9 x C19 (with connector) (full height) 3.2.8 Intelligent Battery Monitoring System The intelligent battery monitoring system consists of the CIM (CIM01C2) and BIM (BIM01C3).
  • Page 52: Cim

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-37 CIM communications cable connecting to a smart ETH gateway 3.2.8.1 CIM CIM is a battery information collection module. It collects battery status data from the downstream BIM groups through wireless communication, and sends the data to the ECC, UPS, and the third-party network management system (NMS) through COM or PoE ports.
  • Page 53 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-38 CIM front view (1) –48 V 0.5 A port (2) PoE port (3) COM_IN port (RS485 (power input) communication input) (4) COM_OUT port (5) DI and DO ports (6) HALL_1–HALL_8...
  • Page 54 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-39 CIM bottom view (1) Fastener (2) Micro SD card slot (3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485 reset) communications address) (5) 12V 2A port (power...
  • Page 55 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-18 –48 V, 0.5 A port pin definitions Definition Description The system provides 48 V DC operating voltage in this – scenario. PoE Port Figure 3-41 PoE port pins...
  • Page 56 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture COM Port Figure 3-42 COM port pins Table 3-20 COM port pin definitions Signal Description RS485+ Two cascaded RS485 communication ports RS485– RS485+ RS485– DI and DO Ports...
  • Page 57 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Definition Signal Status Description Initial Remarks Description Status output signal contact output is open.  Closed: The dry contact output is closed. Current Monitoring Port Figure 3-43 Current monitoring port pins...
  • Page 58 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture BCB Port Figure 3-44 BCB port pins Table 3-23 BCB_1–BCB_4 port pin definitions Definition Signal Status Description Initial Remarks Description Status Monitors  Grounded: BCB Disconnected The four whether the connected.
  • Page 59 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Definition BCB_IN BCB_OUT Status Initial Descrip Signal Signal Description Status tion Description Description output port. port. supports connected. port  Signal output Monitors Grounded: Discon cascadin port for the...
  • Page 60 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicators Table 3-26 Indicator description Indicator Color Meaning Status Description Measure RF_Z Green Wireless Steady No network Requires no communication parameters exist. handling. status (A network is to be created.)
  • Page 61 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Meaning Status Description Measure Huawei technical support. Alarm indicator Steady The actual Check the value number of of BIM number, online devices is the BIM cable...
  • Page 62: Bim

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Default Button Table 3-28 Default button description Name Definition Function Default button Press and hold the Reset to the default IP address button for more than (192.168.0.10) 10s but less than 20s.
  • Page 63 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Panel Ports Figure 3-46 Port pins Table 3-29 Port pin definitions Definition Description BAT_V+ and BAT+ are used for connecting red NTCA wires to positive battery terminals. BAT_V– and...
  • Page 64: Cooling System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Silk Status Description Screen Alarm The BIM is not faulty.  Blinking at Network parameters are being super short cleared. intervals  The BIM is blinking.
  • Page 65: System Description

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.3.1 System Description The cooling system uses air cooled in-row precision air conditioners and an aisle containment for cooling. The air cooled in-row precision air conditioners and equipment cabinets form an aisle containment as shown in Figure 3-47 to separate hot air from cold air.
  • Page 66: Netcol5000-A 25 Kw

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture  Rapid elimination of hot spots: The power of the device can be detected to accelerate respond speed of the air conditioner and by using the air inlet temperature, the partial hot spots that may exist in the Smart Module can be eliminated.
  • Page 67 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-48 Dimensions (unit: mm) Components The indoor unit of the NetCol5000-A consists of a compressor, oil separator, fan, heat exchanger, electronic expansion valve, one-way valve, filter dryer, sight glass, electric heater (optional), electrode humidifier (optional), water pump (optional), and so on.
  • Page 68: Application Environment

    Outdoor unit: IPX5 Altitude 0–1000 m. When the altitude is greater than 1000 meters, the cooling capacity is derated. The maximum operating altitude is 4000 meters. For the detailed derated data, contact Huawei technical support Issue 04 (2017-06-30) Huawei Proprietary and Confidential...
  • Page 69 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Physical Ports Table 3-33 Physical ports Item Specifications Refrigerant liquid pipe Copper pipe, with an outer diameter of 5/8 inch (15.88 mm) and thickness of 1.0 mm, withstanding a pressure not smaller than 4.5 MPa, welding...
  • Page 70 DC pulses and transient current pulses Note: If some conditions are not met, contact Huawei technical support. Water Quality Requirements If the inlet water contains large granules, install a water filtering device at the inlet port to prevent pipe blockage.
  • Page 71: Technical Specifications

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.3.3.3 Technical Specifications Table 3-36 and Table 3-37 show the universal and optional parameters. Table 3-36 Universal parameters Item Specifications Cooling mode Air cooled Refrigerant R410A Air supply mode Horizontal flow ...
  • Page 72: Netcol5000-A 35 Kw

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item NetCol5000-A02 NetCol5000-A02 NetCol5000-A02 NetCol5000-A 5H412D20020E1 5H412D2E120E1 5H412D20020E0 025H412D2E1 20E0 Heating functio Humidi fication functio Pipe Top and bottom Bottom routing mode Conden sate pump Water pump lift In the preceding table, No indicates that the corresponding model does not provide the function.
  • Page 73 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-49 NetCol5000-A in-row precision air conditioner Components of an Indoor Unit The NetCol5000-A consists of the compressor, EC fan, evaporator, air filter, electric heater (optional), electrode humidifier (optional), condensate pump (optional), and low-temperature component (optional).
  • Page 74 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture The positive temperature coefficient (PTC) heater features quick start, large heating capacity, and even heat dissipation. It automatically adjusts heating capacity and has multiple protection mechanisms to ensure the secure and stable running of the equipment.
  • Page 75: Physical Ports

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture drain switch of the switch humidifier cylinder (5) Compressor (6) Compressor (7) Filter dryer (8) Refrigerant pipe angle valve angle valve (9) Automatic (10) Refrigerant (11) Water pump...
  • Page 76: Operating Environment Specifications

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 1/2 inch BSPP: large diameter 20.955 mm; medium diameter 19.793 mm; small diameter 18.631 mm; medium diameter tolerance 0–0.142 mm; small diameter tolerance 0–0.541 mm. 3.3.4.2 Operating Environment Specifications...
  • Page 77 (RCCBs) that are not sensitive to the single-phase DC pulse and transient current pulse. Note: If the requirements are not met, contact Huawei technical support for an optimized plan. Water Quality Requirements...
  • Page 78: Technical Specifications

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture If the inlet water contains large granules, install a water filtering device at the inlet port to prevent pipe blockage. Table 3-42 describes the NetCol5000-A water quality requirements.
  • Page 79: Appearance And Composition Of The Netcol500 Outdoor Unit

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item NetCol5000-A 37.8° C, wet-bulb temperature: 20.8° C, condensing temperature: 45° C). d: Enclosure frames can be used to expand the depth to 1200 mm, while top supports can be used to expand the height to 2200 mm.
  • Page 80 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-52 Appearance In the following chapters, outdoor unit photos are taken from the NetCol500-A072 as examples and are for reference only. Composition The NetCol500 series products consist of a fan driver, a condenser, a rack, and fans, as shown in Figure 3-53.
  • Page 81: Technical Specifications Of The Netcol500 Outdoor Unit

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-53 NetCol500 outdoor unit composition (1) Condenser (2) Fan driver (3) Rack (4) Fans 3.3.6 Technical Specifications of the NetCol500 Outdoor Unit Figure 3-54 shows the dimensions of the NetCol500 series products.
  • Page 82 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-45 Technical Specifications of the NetCol500 series products NetCol5 NetCol50 NetCol50 NetCol50 NetCol50 NetCol50 00-A026 0-A0265S 0-A0325C 0-A0365C 0-A0385C 0-A0725C SC11E0 11E0 11E0 11E0/Net 11E0 11E0 Col500-A...
  • Page 83: Optional) Dehumidifier

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture NetCol5 NetCol50 NetCol50 NetCol50 NetCol50 NetCol50 00-A026 0-A0265S 0-A0325C 0-A0365C 0-A0385C 0-A0725C SC11E0 11E0 11E0 11E0/Net 11E0 11E0 Col500-A 0365S11E Type legs) Certificat RoHS, REACH, CE/CB Running Depends on the indoor unit. For details, refer to the product description of temperat indoor unit user manual.
  • Page 84 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture for each module in the aisle containment at the bottom of the server cabinet near an air conditioner. Figure 3-55 shows the dehumidifier installation position. Figure 3-55 Dehumidifier installation position Figure 3-56 shows a dehumidifier.
  • Page 85 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-56 Dehumidifier (1) Mounting ear (2) Air filter (3) Control panel (4) Castor (5) Water outlet (6) Handle (A) Air intake vent (B) Air exhaust vent Table 3-46 lists the dehumidifier specifications.
  • Page 86: Optional Components

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.3.8 Optional Components The low-temperature component and sunshade are optional for the outdoor unit. 3.3.8.1 Low-Temperature Component Working Principle When the outdoor temperature is below the operating temperature lower limit specified for the product, the condensing pressure of the system for the outdoor unit condenser with natural cooling may still below the safe operating pressure of the compressor.
  • Page 87: Sunshade

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-47 Low-temperature component specifications Item Specifications Heater box power supply 220 V AC to 240 V AC, 1 Ph, 50 Hz/60 Hz Heater box voltage tolerance Rated voltage ± 10% Heater box frequency tolerance Rated frequency ±...
  • Page 88: Controller

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-59 Sunshade dimensions (unit: mm) 3.3.9 Controller The controller for the NetCol5000-A in-row precision air conditioner is composed of a display panel and main control board. Appearance The 7-inch display panel with the true-color touchscreen provides user interfaces for query, setting, monitoring, and maintenance.
  • Page 89: Management System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture  When multiple air conditioners work cooperatively, the controller optimally distributes the heat load to reduce power consumption and provides backup to improve reliability.  Users can monitor, manage, and upgrade one or more air conditioners using the remote management software provided by Huawei.
  • Page 90: System Description

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Function ECC800 WebUI ECC800 App NetEco equipment Monitoring data/alarms for cooling equipment Monitoring data/alarms for environment equipment Monitoring data/alarms for fire extinguishing equipment Access control management Intelligent lighting...
  • Page 91: Server

    3.4.2 Server Tecal RH2288V2 Server The Tecal RH2288V2 rack server (RH2288V2 for short) of Huawei features large-capacity and high-performance. It serves as the monitoring host of the NetEco and is responsible for data processing and analysis.
  • Page 92: Ecc800

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-62 RH2288V2 server The RH2288V2 has the following features:  It has powerful computing and storage capacity and scalability.  It can be flexibly configured with value-added components and has multiple functions.
  • Page 93 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-63 ECC800 (front view) (1) PSU (optional) (2) PSU (optional) (3) Status (4) 3G/4G indicator antenna port (5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW and LAN_1–LAN_2)
  • Page 94 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-65 ECC800 main control module (side view) (1) SIM card slot (2) Micro-SD card slot ECC800 Specifications Table 3-50 ECC800 environmental specifications Item Specifications –20° C to +50° C Working temperature –40°...
  • Page 95 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-52 ECC800 technical specifications Item Specifications  Power input Supports two AC inputs  Rated voltage: 200–240 V AC/100–120 V AC  Rated frequency: 50 Hz/60 Hz Power output ...
  • Page 96 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Name Status Description Green Running status Steady on The power supply is normal, indicator the program is being loaded, or WiFi WPS is pairing. The power supply is abnormal.
  • Page 97 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Name Status Description 0.05s). Table 3-54 PSU indicator description Indicator Color Name Status Description Green Power indicator Steady on The converter has a power input. The converter has no power input or is faulty.
  • Page 98 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Name Status Description The converter delivers no output due to internal faults. The converter is working properly. Wireless Network Pairing (SW) and IP Address Reset (Default) Buttons...
  • Page 99 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Button Function Operation Description Indicator Status Name Description to the default address 192.168.1.10. Communications Ports The ECC800 provides the following communications ports. Figure 3-66 shows the pins of the RJ45 port.
  • Page 100 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-57 RS485 port pin definitions Item Description Pin sequence Pin 1 RS485+ Pin 2 RS485- Pin 3 12 V DC_OUT Pin 4 RS485+ Pin 5 RS485- Pin 6...
  • Page 101 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture There are two DO dry contact outputs (DO_1 and DO_2). Table 3-59 provides the DO port pin definitions. Table 3-59 DO port pin definitions Item Description Pin sequence...
  • Page 102: Lan Switch

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Port Type Description Pin 3 Pin 1 48V+ Pin 2 48VGND 3.4.4 LAN Switch Figure 3-67 shows an S5320 LAN switch. Figure 3-67 S5320 LAN switch Table 3-62 lists the specifications of an S5320 LAN switch.
  • Page 103: Video System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.4.5 Video System The video system consists of the camera and VCN500, implementing real-time monitoring, video recording, and playback. 3.4.5.1 IP Camera The IPC6325-WD-VR network camera (IPC6325 camera for short) is a two-megapixel wide dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.
  • Page 104: Vcn500

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications applicable to DC/AC adapter and PoE hot backup Protection level IP66; complying with IEC 60529 Vandal-proof class IK10; complying with IEC 62262 3.4.5.2 VCN500 Figure 3-69 shows a VCN500.
  • Page 105: Skylight Control System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Description RAID controller card The VCN500 does not have a RAID controller card on its mainboard. Type and number of One 1 GHz CPU, max. 10 MB cache...
  • Page 106 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-70 shows a skylight actuator. Figure 3-70 Skylight actuator (1) LOCK/GND (2) BUTTON/GND (3) AI/DI_1 sensor (4) AI/DI_2 sensor magnetic lock DO window open button DI input port...
  • Page 107 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications signals; smoke detection signals also supported DO output One 12 V DC power output for controlling the skylight magnetic lock; driving six skylight magnetic locks simultaneously...
  • Page 108: Access Control System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicat Name Status Description No system alarm is generated. RF_Z Gree Communication Steady on No network parameters exist, or a status indicator network is to be created. Blinking at...
  • Page 109 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-71 Access actuator (1) 48 V power port (2) PoE port (3) RS485 port COM2 (4) RS485 port COM1 (5) Address DIP switch (6) Status indicator (7) BLINK button...
  • Page 110 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications button DO output One 12 V DC power output that controls magnetic locks, phoenix terminal DI input One DI input port for connecting to the door status switch...
  • Page 111 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicato Color Name Status Description Blinking The indicator blinks at super short intervals for 0.5s (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s.
  • Page 112: Aisle Access Control

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.4.7.2 Aisle Access Control The aisle access control system applies to the aisle containment. It provides monitoring and data for devices and personnel moving into or out of the aisle containment. It can support the fingerprint and card reader with a keypad, fingerprint and card reader, and card reader with a keypad.
  • Page 113 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications  Working status Standby: The blue indicator is on, and the green indicator for the fingerprint reader is steady on.  Fingerprint collection: The red indicator for the fingerprint reader is on.
  • Page 114 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications Operating current Rated 300 mA± 5% Supported card IC card Authorized storage A maximum of 3000 authorized users, with a maximum of 6000 fingerprints Communications mode RS485 and Wiegand communications ports ...
  • Page 115 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-74 Specifications of a card reader with a keypad Item Specifications Dimensions (H x W x D) 114 mm x 63 mm x 25 mm Operating voltage Operating voltage range: 10.8–13.2 V DC;...
  • Page 116: Cabinet Access Control

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture  The access control system consists of an access actuator, fingerprint reader with a keypad, magnetic lock, and exit button.  The emergency door release button can disconnect the power supply to the electronic lock to open the door in case of emergency.
  • Page 117: Water Sensor

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture (Optional) Mechanical Code Lock Figure 3-78 shows a mechanical code lock. Figure 3-78 Mechanical code lock Functions and features:  The cabinet door can be opened with only the key and without the password.
  • Page 118: Optional) Smoke Detector

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-79 Water sensor and water detection cable Table 3-76 Technical specifications of a water sensor Item Specifications Operating voltage 12 V DC (9–16 V DC) Output when no liquid exists...
  • Page 119: Optional) Temperature Sensor

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-80 Smoke detector Table 3-77 Technical specifications of a smoke detector Item Specifications Operating voltage 9–16 V DC Quiescent current < 8 mA Alarm current < 35 mA...
  • Page 120: Multi-Functional Sensor

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-78 lists the temperature sensor specifications. Table 3-78 Temperature sensor specifications Item Specifications –20° C to +70° C Measurement range Measurement precision ± 1° C –10° C to +55° C...
  • Page 121 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications PoE port One PoE port that complies with IEEE802.3AT RS485 port One RS485 port is reserved. DI input One DI input port, 12 V DC power input...
  • Page 122: Rack Environment Unit

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicat Name Status Description No system alarm is generated. RF_Z Gree Communication Steady on No network parameters exist, or a status indicator network is to be created. Blinking at...
  • Page 123 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Specifications Table 3-81 lists the technical specifications for the rack environment unit. Table 3-81 Technical specifications for the rack environment unit Item Specifications Power input  DC input: Phoenix terminal, with input voltage of 36–60 V DC ...
  • Page 124: Smart Eth Gateway

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Name Status Description for 0.125s). Blinking The indicator blinks at super short intervals for 0.5s (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s.
  • Page 125 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-83 Technical specifications for a smart ETH gateway Item Specifications Power input PWR_IN D-type power input terminal, for power cascading, input voltage range: 45–55 V DC Power output ...
  • Page 126: Wifi Converter

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicat Name Status Description Alarm indicator Steady on A system failure alarm is generated. No system alarm is generated. 3.4.14 WiFi Converter The WiFi converter is used in a smart module to convert PoE signals into WiFi signals for communicating with devices such as the pad and mobile phone.
  • Page 127 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications  WiFi function 2.4 GHz frequency, two antennas, supporting eight STA connections, 50 m WiFi coverage (no blockage)  Supports the WPS button. PoE port One PoE port, complying with IEEE802.3AT, 25.5 W...
  • Page 128: Alarm Beacon

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicat Name Status Description turns off after blinking for 2 minutes. If the matching is successful, the WPS indicator turns off. 3.4.15 Alarm Beacon The alarm beacon is installed at the periphery of the aisle containment. When a fire occurs or smokes are generated in the micro-modular equipment room, the alarm beacon generates an audible signal and flashes to inform operators of fire and security risks.
  • Page 129: Eth Converter

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-88 Technical specifications of an alarm beacon Item Specifications RJ45 port, input voltage 9–16 V DC, operating current ≤ 400 Power input ≥ 100 ± 3 dB/30 cm Sound pressure ≥...
  • Page 130 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications  PoE input: 36–60 V DC power input RS485 or Provides two RS485/CAN ports. The default communications rate for the control area RS485 port is 9600 bit/s, and that for the CAN port is 125 kbit/s. Both network ports match the RJ45 terminal shared by RS485 and CAN.
  • Page 131: Pad

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicator Color Name Status Description No system alarm is generated. 3.4.17 Pad The pad allows the wireless access from the data center management system. You can monitor the equipment in the data center and environmental parameters in real time over the APP Figure 3-88 shows a pad.
  • Page 132: Cable Management System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications  Store Machine: 16 GB  Memory: 2 GB LPDDR3  Extension card: microSD, a maximum of 64 GB supported  Button/Port Power switch and volume button ...
  • Page 133 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Table 3-93 Cable manager specifications Dimensions (H x W x D) Weight Space Occupied 43.6 mm x 482.6 mm x 91 0.56 kg Cable Ring A cable ring is installed on a side post in the cabinet to secure vertically routed cables.
  • Page 134: Lighting System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-91 Cable tray Table 3-95 Cable tray specifications Dimensions (H x W x D) Weight Space Occupied 43.6 mm x 482.6 mm x 250 1.89 kg 3.6 Lighting System The lighting system consists of an AC actuator and aisle lights which can be configured based on the actual situation.
  • Page 135 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-92 AC actuator (1) AC OUT2 port (2) AC OUT1 port (3) AC IN port (4) Status indicator (5) BLINK button (6) AI/DI dry (7) COM1–2 RS485...
  • Page 136 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Item Specifications networking.  Hold down the button for more than 6 seconds to clear network parameters. Indicators Table 3-97 describes the indicators on the AC actuator. Table 3-97 AC actuator indicators...
  • Page 137: Aisle Light

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Indicat Name Status Description then off for 0.05s). Blinking The AC actuator is searching for a intermittently network (the indicator blinks at at super short super short intervals for 0.5s and intervals then turns off for 0.5s).
  • Page 138: Surge Protection And Grounding System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture 3.7 Surge Protection and Grounding System The surge protection and grounding system of the smart module consists of the surge protection solution and grounding solution. 3.7.1 Surge Protection Solution The smart module uses the following surge protection solution.
  • Page 139 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture As shown in Figure 3-94 and Figure 3-95: Each cabinet in the smart module connects to the nearest ground grid using ground cables with the minimum cross-sectional area of 16 mm Use 100 x 0.3 copper foils or copper braids with a cross-sectional area of 25 mm...
  • Page 140: Integrated Cabling System

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-97 Equipotential cable connections for dual-row cabinets (two branch ground copper bars) 3.8 Integrated Cabling System The integrated cabling system of the smart module includes cable routing devices and cables.
  • Page 141 FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-98 Diagram for routing cables (1) Smart ETH gateway (2) Signal cable (3) Optical fiber (4) Network cabinet (5) Power cable (6) PDC When the distance between two modules is 1200 mm, the power cables are routed through the cable tray located on the top of the PDC to the other module, and the signal cable is routed through the cable tray located on the top of the network cabinet to the other module.
  • Page 142: Cables

    FusionModule2000 Smart Modular Data Center Product Description (380 V) 3 System Architecture Figure 3-99 Diagram for routing cables between modules (1) Power cable (2) Signal cable (3) Optical fiber 3.8.2 Cables Power Cables The power cables include power cables to UPSs, battery cabinets, air conditioners, and PDU2000s.
  • Page 143: A Equipment Derating Coefficients

    FusionModule2000 Smart Modular Data Center Product Description (380 V) A Equipment Derating Coefficients Equipment Derating Coefficients Table A-1lists the derating coefficients of the UPS5000 Table A-1are based on the dry air density being 1.225 kg/m (sea level + 15º C).
  • Page 144 FusionModule2000 Smart Modular Data Center Product Description (380 V) A Equipment Derating Coefficients Altitude (unit: m) Density Air Volume Cooling Capacity Coefficient Coefficient Coefficient 1000 0.887 0.887 0.940 1500 0.835 0.835 0.909 2000 0.785 0.785 0.878 2500 0.737 0.737 0.846 3000 0.692...
  • Page 145: B Acronyms And Abbreviations

    FusionModule2000 Smart Modular Data Center Product Description (380 V) B Acronyms and Abbreviations Acronyms and Abbreviations alternate current Auto Transformer Switch Battery Circuit Breaker Battery control I/O board Battery Interface Module BSPP British Standard Pipe Parallel Thread Controller Area Network Conformité...
  • Page 146 FusionModule2000 Smart Modular Data Center Product Description (380 V) B Acronyms and Abbreviations Fast Ethernet iBAT ibattery Integrated Circuit Internet Data Center Internet Technology Liquid Crystal Display Light Emitting Diode MTBF mean time between failures MTTR mean time to repair...
  • Page 147 FusionModule2000 Smart Modular Data Center Product Description (380 V) B Acronyms and Abbreviations SNMP Simple Network Management Protocol surge protective device Universal Series Bus uninterruptible power system Video Cloud Node WiFi Wireless Fidelity Issue 04 (2017-06-30) Huawei Proprietary and Confidential...

Table of Contents