Cisco ONS 15454 Hardware Installation Manual page 60

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Mounting Multiple Nodes
Figure 11: Three-Shelf ONS 15454 ETSI Bay Assembly
Warning
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be bolted to the
floor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip
over. Statement 1048
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations. Statement 1045
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than: 10A-20A, 100-240 VAC~. Statement 1005
Warning
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
recommended ambient temperature of: 45 degrees C (113 degrees F). Statement 1047
Warning
Take care when connecting units to the supply circuit so that wiring is not overloaded. Statement 1018
Cisco ONS 15454 Hardware Installation Guide
30
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf