Cisco ONS 15454 Hardware Installation Manual page 42

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

User Supplied Materials
Table 2: User Supplied Materials
User
Supplied
Material
Bit error
rate (BER)
tester
BNC
insertion
tool
Cables
Cisco ONS 15454 Hardware Installation Guide
12
Preparing to Install the ONS 15454 (ANSI and ETSI), ONS 15454 M2 and ONS 15454 M6 Shelf
ONS 15454
ANSI
Bit error rate (BER) tester, DS-1
and DS-3
ANSI
BNC insertion tool
ANSI
• Power cable (from fuse and
alarm panel to assembly),
#10 AWG, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for all
alarm connections, #22 or
#24 AWG (0.51 mm² or 0.64
mm²), solid tinned.
• 100-ohm shielded building
integrated timing supply
(BITS) clock cable pair #22
or #24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
• Shielded coaxial cable
terminated with SMB or
BNC connectors for DS-3
cards.
• Shielded ABAM cable
terminated with AMP Champ
connectors or unterminated
for DS1N-14 cards with #22
or #24 AWG (0.51 mm² or
0.64 mm²) ground wire
(typically about two ft [61
cm] in length)
• 6-pair #29 AWG
double-shielded cable
ONS 15454 M2
ANSI
• Power cable (from fuse
and alarm panel to
assembly), #12 AWG
or larger, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for
all alarm connections,
#22 or #24 AWG (0.51
mm² or 0.64 mm²),
solid tinned.
• 100-ohm shielded
building integrated
timing supply (BITS)
clock cable pair #22 or
#24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
ETSI
• Copper ground cable
13.3-mm² (#6 AWG)
stranded, specified for
up to 90 degrees
Celsius (194 degrees
Fahrenheit)
• Alarm cable pairs for
all alarm connections,
0.51 mm² or 0.64 mm²
(#22 or #24 AWG),
solid-tinned
ONS 15454 M6
ANSI
• Power cable (from fuse
and alarm panel to
assembly), #8 AWG or
larger, copper
conductors, 194 degrees
Fahrenheit (90 degrees
Celsius).
• Ground cable #6 AWG
stranded
• Alarm cable pairs for all
alarm connections, #22
or #24 AWG (0.51 mm²
or 0.64 mm²), solid
tinned.
• 100-ohm shielded
building integrated
timing supply (BITS)
clock cable pair #22 or
#24 AWG (0.51 mm² or
0.64 mm²), twisted-pair
T1-type
ETSI
• Copper ground cable
13.3-mm² (#6 AWG)
stranded, specified for
up to 90 degrees Celsius
(194 degrees
Fahrenheit)
• Alarm cable pairs for all
alarm connections, 0.51
mm² or 0.64 mm² (#22
or #24 AWG),
solid-tinned