Installing the ONS 15454 M2 Shelf
DLP-G584 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M2 Shelf for ANSI Rack Configuration
Note
The mounting brackets can be installed in the front or the middle position of the chassis.
Procedure
Step 1
Place the narrow side of the 23-inch mounting bracket flush against the shelf (see the following figure). The
wider side of the mounting bracket should be towards the front of the shelf.
Step 2
Align the mounting bracket screw holes against the shelf screw holes.
Step 3
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 4
Repeat steps 1 through 3 for mounting the bracket on the opposite side.
Figure 122: Mounting the Brackets on the ONS 15454 M2 shelf for a 23-inch (584.2-mm) ANSI Configuration
Step 5
Return to your originating procedure (NTP).
DLP-G584 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M2 Shelf
for ANSI Rack Configuration
Purpose
Tools/Equipment
This task mounts the 23-inch brackets with air deflectors (front-to-back) on the
ONS 15454 M2 shelf for ANSI rack configuration.
In an ANSI rack, the air deflectors can be mounted only in the 23-inch
Note
rack configuration and in the front position of the chassis.
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
Cisco ONS 15454 Hardware Installation Guide
199