Table 47: ONS 15454 M6 DC Power Specifications
DC Power
Rating
Module
15454-M6-DC
30
Amp
15454-M6-DC20
20
Amp
15454-M6-DC40
40
Amp
Note
When the ONS 15454 M6 shelf is powered at –60 VDC (nominal), only these cards can be installed: TNC,
OPT-AMP-C, OPT-AMP-17-C, OPT-EDFA-17, OPT-EDFA-24, 17 SMR9 FS, 24 SMR9 FS, 34 SMR9 FS,
SMR20 FS, SMR20 FS CV, 12-AD-FS, 16-AD-FS, 100GS-CK-LC, MR-MXP cards, and the
15454-M6-ECU-60 card.
• 15454-M6-DC, 15454-M6-DC20, and 15454-M6-DC40 shelf power consumption (configuration
• When you use the 60V DC power module for ONS 15454 M6, you must go to CTC (shelf-view)
• Power terminals—DSUB 3 poles for ETSI applications and terminal block, double pole for ANSI
• External fuse must not exceed 40 A
Nominal
Current
Input Voltage Range
Voltage
–48 VDC
30
–40.5 to –57.6 VDC
Amp
–60 VDC
24
–50 to –72 VDC
Amp
–48 VDC
20
–40.5 to –57.6 VDC
Amp
–60 VDC
16
–50 to –72 VDC
Amp
-48 VDC
40
–40.5 to –57.6 VDC
Amp
-60 VDC
32
–50 to –72 VDC
Amp
dependent):
• 130 W with 15454-M6-FTA Fan Tray, LCD, and ECU module
• 140 W with 15454-M6-FTA2 Fan Tray, LCD, and ECU module
Provisioning > General > Power Monitor and set the following threshold values:
• ELWBATVG (Extreme Low Battery Voltage)=-50 Vdc
• LWBATVG (Low Battery Voltage)=-50 Vdc
• HIBATVG (High Battery Voltage)=-72 Vdc
• EHIBATVG (Extreme High Battery Voltage)=-72 Vdc
applications.
Maximum
Load
1440 W
960 W
1920 W