NTP-G256 Install Power and Ground to the ONS 15454 M6 Shelf
NTP-G256 Install Power and Ground to the ONS 15454 M6 Shelf
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Warning
To ensure safety of personnel and equipment, do not connect any power cables into the power module
until the module is completely installed into the chassis. Statement 389
Warning
To reduce the risk of electric shock, switch on the power only after the power cord is completely installed
into the power module. Statement 390
Cisco ONS 15454 Hardware Installation Guide
370
This procedure installs power feeds and grounds the ONS 15454 M6 system.
ANSI and ETSI:
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Screws
• Ground cable 13.3-mm² (#6 AWG) stranded
• Listed pressure dual-holes lugs suitable for #8 AWG copper conductors
• Wire cutters
• Wire strippers
• Crimp tool
• Fuse panel
ANSI only:
• Power cable (from fuse and alarm panel to assembly), #8 AWG, copper
conductors, 194 degrees F [90 degrees C])
• Wire wrapper
ETSI only:
• Power cable (from fuse panel to power modules), shipped with the ONS
15454 M6
• Two-hole grounding lug, shipped with the ONS 15454 M6
NTP-G524 Install the Power Modules in the ONS 15454 M6 Shelf , on page
355.
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, see the
for Cisco CPT and Cisco ONS
Required
Onsite
None
Installing the ONS 15454 M6 Shelf
Electrostatic Discharge and Grounding Guide
Platforms.