Cisco ONS 15454 Hardware Installation Manual page 333

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Installing the ONS 15454 M6 Shelf
DLP-G561 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration
Step 6
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 7
Place the 23-inch mounting bracket flush in the front position (see Diagram 1 of
Brackets with Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration, on
page
304) or in the middle position (see Diagram 3 of
(Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration, on page
side of the chassis.
Step 8
Align the screw holes on the 23-inch mounting bracket with the screw holes on the right side of the chassis.
Step 9
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 10
Place the 23-inch mounting bracket flush in the front position (see Diagram 1 of
Brackets with Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration, on
page
304) or in the middle position (see Diagram 3 of
(Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration, on page
of the chassis.
Step 11
Align the screw holes on the 23-inch mounting bracket with the screw holes on the left side of the chassis.
Step 12
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Figure 203: Mounting the Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for the ANSI rack Configuration
Figure 204: Mounting the
Figure 204: Mounting the Brackets with Air Deflectors
Figure 204: Mounting the
Figure 204: Mounting the Brackets with Air Deflectors
Cisco ONS 15454 Hardware Installation Guide
304) against the right
304) against the left side
303