Installing the ONS 15454 M2 Shelf
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than: 10A-20A, 100-240 VAC~. Statement 1005
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement
1022
Warning
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit. Statement 1028
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454. For detailed instructions
on how to wear the ESD wristband, refer to the
and Cisco ONS
Procedure
Step 1
Verify that the correct fuse panel is installed in the top mounting space:
• For a DC power supply, the fuse rating must not exceed 15A.
• For an AC power supply, the fuse rating must not exceed 10A, 15A, or 20A. For low input voltage ranges,
Step 2
Depending on the shelf and the power module installed, complete the necessary tasks:
Step 3
Connect the office ground to the ONS 15454 M2 shelf. For detailed instructions on grounding, refer to the
Electrostatic Discharge and Grounding Guide for Cisco CPT and Cisco ONS Platforms
Step 4
Complete the
Step 5
Continue with the
Stop. You have completed this procedure.

DLP-G596 Connect Office Power (AC) to the ONS 15454 M2 Shelf

Purpose
Platforms.
100V to 127Vac, the branch circuit protection must not be rated more than 20A. The overcurrent/short
circuit protection must be in accordance with local and national electrical codes.
DLP-G596 Connect Office Power (AC) to the ONS 15454 M2 Shelf, on page 241
DLP-G597 Connect Office Power (DC) to the ONS 15454 M2 Shelf (ANSI Only), on page 244
DLP-G598 Connect Office Power (DC) to the ONS 15454 M2 Shelf (ETSI Only), on page 249
DLP-G600 Turn On and Verify DC Office Power on the ONS 15454 M2 Shelf, on page
NTP-G268 Install the Fan-Tray Assembly in the ONS 15454 M2 Shelf, on page
This task connects AC power to the ONS 15454 M2 shelf.
DLP-G596 Connect Office Power (AC) to the ONS 15454 M2 Shelf