Return to your originating procedure (NTP).
Air Flow Performance of ONS 15454 M6
The tables below summarizes the air flow performance of ONS 15454 M6:
Case
Side to Side
ETSI Front to Rear
ETSI Front to Side
ANSI Front to
Rear
ANSI Front to Side
Case
Deflector
Worst Line Card
Configuration
Slot (#7) Flow,
CFM
9600 RPM
(27°C)
No deflectors
16
Inlet and Outlet
8.2
Only Inlet
12.2
Inlet and Outlet
13.4
Only Inlet
14.8
Deflector Configuration
Bulk Chassis Flow, CFM
9600 RPM
Air Flow Performance of ONS 15454 M6
Worst Controller
Card Slot (#8) Flow,
CFM
13500 RPM (40°C
9600 RPM
and 55°C)
(27°C)
22.4
14.9
11.2
6.9
16.8
12.7
18.7
10.6
20.7
14.1
13500 RPM
Cisco ONS 15454 Hardware Installation Guide
13500 RPM
(40°C and
55°C)
21
10
18.4
14.7
19.7