Mounting A Single Node - Cisco ONS 15454 Hardware Installation Manual

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Installing the ONS 15454 M12 (ANSI and ETSI) Shelf

Mounting a Single Node

Figure 9: ONS 15454 ETSI Shelf Dimensions
Mounting a Single Node
The ONS 15454 ETSI requires 616.5 mm (24.24 inch) minimum of vertical rack space and 25 mm (1 inch)
below the installed shelf to allow air flow to the fan intake. If a second ONS 15454 ETSI is installed above
a shelf, the air ramp between the shelves provides space for air flow. To ensure the mounting is secure, use
two to four M6 mounting screws for each side of the shelf. A shelf should be mounted at the bottom of the
rack if it is the only unit in the rack.
The following figure shows the rack mounting position for the ONS 15454 ETSI shelf.
Cisco ONS 15454 Hardware Installation Guide
28