Appendix 2.16.3.3 Troubleshooting for each warning No.

Scale feedback error
Warning No.
An excessive difference in feedback amount was detected between the main side detector and the MPI scale in MPI scale
96
absolute position detection system.
Investigation details
Check if there is any abnormality in the
detector's ambient environment.
1
(Ex. Ambient temperature, noise,
grounding)
2
Check the repeatability.
Warning No.
Scale offset error
97
An error was detected in the offset data that is read at the NC power-ON in MPI scale absolute position detection system.
Investigation details
Check if there is any abnormality in the
detector's ambient environment.
1
(Ex. Ambient temperature, noise,
grounding)
2
Check the repeatability.
Incremental detector/magnetic pole shift warning
Warning No.
For the incremental detector, an error was detected in the magnetic pole shift amount set in the magnetic pole shift amount
9B
parameter "SV028".
Investigation details
Check if there is any abnormality in the
detector's ambient environment.
1
(Ex. Ambient temperature, noise,
grounding)
2
Check the repeatability.
Absolute position detector: Revolution counter error
Warning No.
An error was detected in the revolution counter of the absolute position detector. The absolute position data cannot be
9E
compensated.
Investigation details
Check if there is any abnormality in the
detector's ambient environment.
1
(Ex. Ambient temperature, noise,
grounding)
2
Check the repeatability.
Investigation results
Take remedies according to the causes of the abnormality in the ambient environment.
Occurs frequently.
Is not repeated.
Investigation results
Take remedies according to the causes of the abnormality in the ambient environment.
Occurs frequently.
Is not repeated.
Investigation results
Take remedies according to the causes of the abnormality in the ambient environment.
Occurs occasionally.
Is not repeated.
Investigation results
Take remedies according to the causes of the abnormality in the ambient environment.
Occurs frequently.
Is not repeated.
Appendix 2.16 Troubleshooting
Remedies
Replace the detector.
Check the investigation item No. 1.
Remedies
Replace the detector.
Check the investigation item No. 1.
Remedies
Execute magnetic pole detection control
again and reset SV028.
Check the investigation item No. 1.
Remedies
Replace the detector.
Check the investigation item No. 1.
C70 Setup Manual
SV SP
SV SP
SV SP
SV SP
585