MITSUBISHI CNC
2 GOT Initial Setup

2.2.2.2 Setting Ethernet Connection (for GT15)

This section explains the setting procedure for Ethernet connection of GOT1000 Series GT15.
Mount the Ethernet communication unit on the GOT rear slot IF-1, and then connect it with the CNC CPU module with an
Ethernet cable.
The following two IP addresses need to be set in order to establish the Ethernet connection.
GOT's IP address (192.168.1.1 in this manual)
CNC CPU module's IP address (192.168.1.2)
GT Designer2
Rear view
IF-1
Insert the
Ethernet module
(Note 1) When connecting to a personal computer and a module with USB interface, an electric shock or a module
failure may occur depending on the model of a personal computer or the service condition.
Be sure to refer to "Items related to connection" on "Precautions for Safety" before connecting them.
(Note 2) When mounting the module on the GOT rear slot IF-2, set the "Extend I/F-2" items in later communication
setting.
(Note 3) Unless there is a specific reason, set the CNC CPU default IP address (192.168.1.2). If any other IP adress is
set, the backup data created with GOT backup and restore function cannot be restored to the replaced CNC
CPU module, which has a default IP address.
34
GOT1000 Series GT15
or
USB
GT09-C20USB-5P
GT09-C30USB-5P
IF-2
(SVGA / XGA)
IP address: 192.168.1.1
100BASE-T
Cross
CNC CPU
Q173NCCPU
IP address: 192.168.1.2
Ethernet module
GT15-J71E71-100
100BASE-T
or
Straight