Appendix 1 Explanation of Parameters
【#29016(PR)】 Status Data:Word Area Local Node Inform.
Status data: Word area local node information area
Set a device to store the following data:
<1st word: Local node information area>
Stores the parameter information.
(This is enabled when "#29013 Status Data: Bit Area Local Node Inform." 2nd word area bit1 is set
to "0".)
15
<2nd word: Local node information area>
Stores the data unit applied in the message data area.
0: Word unit
1: Byte unit
<13th word: Local node information area>
Indicates the node No. of the FL-net module.
1 to 249: Node No.
<14th word: Local node information area>
Indicates the mode switch status of the FL-net module.
0: Online
1: Offline
2: Loopback test
3: Hardware test
Others: Setting error
<15th, 16th word: Local node information area>
Indicates the IP address status of the FL-net module.
<17th word: Local node information area>
Indicates switches setting status.
0: Normal
1 and later: Error code
<18th word: Local node information area>
Indicates the Ethernet interface owned by the local node module.
bit0: 10BASE2 (0: No, 1: Yes)
bit1: 10BASE5 (0: No, 1: Yes)
bit2: 10BASE-T (0: No, 1: Yes)
<19th word: Local node information area>
Local node communication status: Indicates data link (cyclic transmission) of local node.
0: During data link
3: Disconnecting (Parameter error detection)
4: Disconnecting (Token monitoring time out)
5: Disconnecting (Node number multiplexing detection)
6: Disconnecting (Receive wait status)
7: Disconnecting (Invalid communication detected)
FE: Initializing
FF: Resetting
<20th word: Local node information area>
Indicates FL-net (OPCN-2) protocol version.