【#29008(PR)】 Token Watch Time Out Token watch time-out time
Set the token watch time-out time.
The standard setting is "50".
---Setting range---
0 to 65535
【#29009(PR)】 Min. Permissible Frame Duration Minimum permissible frame interval
Set the minimum permissible frame interval.
The standard setting is "0".
---Setting range---
0 to 50
【#29010(PR)】 Message Data Unit Select (0:Word 1:Byte) Message data unit select
Select the data unit in treating message data.
The standard setting is "0".
0: Word unit
1: Byte unit
【#29012(PR)】 Status Data: Bit Area Specified Inform.
Status data: Bit area instruct information area
Set the device to store the following data:
bit9: buffer memory log information area clear
Instructs clearing of the buffer memory log information area (address: A80H to B38H).
0: No clear instruction / 1: Clear instruction
---Setting range---
Within the number of device points set in the PC parameter's device setting.
C70 Setup Manual
Appendix 1.8 FL-net Parameters