L11 DN INIT. ERR. 2 03 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The lower byte of the slave node No. in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set it between 0 and 63.
L11 DN INIT. ERR. 2 04 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The higher byte of the slave node No. in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set it between 01H and 04H, or to 80H.
L11 DN INIT. ERR. 2 05 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The connection type in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set it to one of the following: 0001H, 0002H, 0004H, or 0008H.
L11 DN INIT. ERR. 2 06 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- A slave node having the same node No. as the node No. of the local node is set in the buffer
memory.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set non-duplicate node Nos. in all nodes.
L11 DN INIT. ERR. 2 07 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- No slave node has been set.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set at least one slave node.
L11 DN INIT. ERR. 2 08 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The total input data length of all slave nodes is too long.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Reduce the total data length of all slave nodes to 512 bytes or less.
L11 DN INIT. ERR. 2 09 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The total output data length of all slave nodes is too long.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Reduce the total data length of all slave nodes to 512 bytes or less.