8.7.4 How Can I Set and Add a UPS5000 (Modbus-RTU)?

Prerequisites
Issue 04 (2021-10-09)
Log in to the ECC800-Pro WebUI as an administrator.
Add a UPS2000G_L.
Table 8-4 Adding a UPS2000G_L
Path
Parameter
Choose
Device
System
attribute
Settings >
Device type
Device
Management
and click Add
Connect To
Device.
Communicati
ons Port
Device
Address
Click Test Connect to check whether the UPS2000G_L connects to the
ECC800-Pro properly.
If the UPS2000G_L connects to the ECC800-Pro successfully, click
Confirm. The connected devices are displayed in the Number of
connected devices list.
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
One end of the straight-through cable has been connected to the RS485 port
on the UPS5000 monitoring module, and the other end has been connected
to the COM port on the ETH converter.
When connecting devices, you are advised to add devices one by one and
ensure that the view is consistent with the real object. If all devices have been
added and powered on, only the BLINK function of the ETH converter can be
used to identify the mapping between the UPS5000 and ETH converter.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select UPS from the drop-down list box.
Select UPS2000G_L from the drop-down
list box.
Select ECC800 from the drop-down list
box.
Select COM2 from the drop-down list box.
NOTE
The setting example indicates that the
UPS2000G_L is connected to the COM2 port on
the ECC800-Pro. If the UPS2000G_L is
connected to another port, select the number of
the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the UPS2000G_L based on the
actual situation.