Huawei SmartDC V100R021C10 User Manual page 67

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Item
Test button
(smoke sensor
test button)
E-label
Indicators
Table 3-47 Description of the indicators on the multi-functional sensor
Indicator
RUN
ALM
RF_Z
Issue 04 (2021-10-09)
Specifications
Supports the smoke sensor test.
Hold down the button for 3s to trigger a smoke alarm, and
release the button to stop the smoke alarm.
Supported
Color
Name
Green
Module
running
status
indicator
Red
Alarm
indicator
Green
Communicat
ion status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Blinking at
The multi-functional sensor
long
successfully registers with
intervals
the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
The multi-functional sensor
short
fails to register with the
intervals
ECC800-Pro or the
communication fails (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
Steady on
No network parameters
exist, or a network is to be
created.
Blinking at
A network is set up, and no
long
node access is allowed (the
intervals
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
3 Device Description
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800

Table of Contents