How Can I Set And Add A T/H Sensor (Bom Number: 33010516) - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 3 Check the monitoring functions of the temperature sensor.
Table 8-34 Function commissioning
Check Method
Path: Monitoring >
Cabinet> IT Cabinet n > T/H
sensor n
----End
8.7.37 How Can I Set and Add a T/H Sensor (BOM Number:
33010516)?
If a T/H sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port
on the T/H sensor, and the other end has been connected to the COM port on the
ECC800-Pro or the UIM20A expansion module.
Context
This section describes how to set and add a T/H sensor by using the COM port on
the ECC800-Pro as an example.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1 to 6 of the DIP switch specify the device address in binary mode.
ON indicates 1, and OFF indicates 0.
Table 8-35 Setting a device address
Address
1
2
3
Issue 04 (2021-10-09)
Figure 8-17 Device connection
Toggle
Switch 1
ON
OFF
ON
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
You can view the current cabinet temperature.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
8 FAQ
Toggle
Switch 6
OFF
OFF
OFF
348