ECC800 Data Center Controller
User Manual
Table 6-66 Information obtained from the NMS
Item
SNMP version
SNMP port number
● Read community
● Write
● User name
● MD5/SHA
● DES/AES
Trap target address
Trap port
Context
Procedure
Step 1 Apply to the equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 6-67 IP parameters
Path
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
Issue 04 (2021-10-09)
Default
Value
SNMPv3
161
-
name
community
name
-
password
password
-
162
SNMPv3 parameters should be set before connecting the ECC800-Pro to the
NMS. These parameters are required for setting up the ECC800-Pro on the
NMS.
SNMPv1 and SNMPv2c are insecure. Therefore, SNMPv3 is recommended.
This section uses SNMPv3 as an example.
Parameter
IP
Subnet
mask
Copyright © Huawei Technologies Co., Ltd.
Description
SNMP version and port number used by the
ECC800-Pro and NMS. The SNMP versions
include SNMPv1, SNMPv2c, and SNMPv3.
If you use SNMPv1 or SNMPv2c, enter the
read and write community names that comply
with the NMS. Otherwise, the ECC800-Pro will
not connect to the NMS. The read community
name must be different from the write
community name.
To enhance the security, you need a user
name and password for authentication if you
use SNMPv3. After the authentication
succeeds, the ECC800-Pro can communicate
with the NMS.
IP address of the NMS server.
Port defined by the user.
Default
Setting
Value
192.168.8.1
Set this parameter based on the IP
0
address assigned by the network
administrator.
255.255.25
Set this parameter based on the
5.0
subnet mask assigned by the network
administrator.
6 Feature Description