How Can I Export Historical Data And Device Data - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
Step 3 Set Device type to ECC800, set Device name to ECC800, and click OK.
Step 4 On the query result tab page, set the new signal name of AI/DI_3 to Smoke and
click Submit.
Step 5 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3 Port
Settings. Check that the signal name of AI/DI_3 has been changed to Smoke.
----End
8.17 How Can I Export Historical Data and Device
Data?
Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Select Query > Export Data.
Step 3 (Optional) Select Encryption password and enter an encryption password.
Step 4 Export historical data and local data of southbound devices, and select a save path
to save the exported data to the PC.
Issue 04 (2021-10-09)
NO TE
After the signal name is changed, the original name in the alarm, collection, and settings is
changed accordingly.
Export Historical Data: You can export historical alarms, active alarms,
performance data, operation logs, and access events of the system for viewing
and analyzing events.
Export Device Data: You can export device data in system.
If Encryption Password is selected, the exported data package will be
encrypted, and you need to enter the encryption password to decompress the
data package. To ensure data security, you are advised to select Encryption
password.
NO TE
Record the password for decompressing the data package.