Table 3-25 Technical specifications for a smart ETH gateway
Item
Power input
Power
output
FE port
PoE port
BLINK
button
Indicators
Table 3-26 Indicators on a smart ETH gateway
Indicator
PWR
RUN
Issue 04 (2021-10-09)
Specifications
PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC);
power of cascaded smart ETH gateways: max (25 A, 48 V DC)
● PWR_OUT D-type power output terminal, for power
cascading, output voltage range: 45–55 V DC
● 48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output
voltage range: 45–55 V DC
Two FE ports, RJ45 terminal with an indicator, 10/100M
communication rate, for the cascading between smart ETH
gateways and the communication with the upper computer
Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
If you press the BLINK button, the RUN indicator blinks
intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 5 seconds.
Color
Name
Green
Power
input status
indicator
Green
Module
running
status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with
intervals
the ECC800-Pro and the
software runs properly
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).
3 Device Description