8.1.8.5 How to Set and Add a PDU8000 (over Modbus RTU)?

Prerequisites
One end of the straight-through cable has been connected to the COM port on the PDU8000,
and the other end has been connected to the COM port on the ECC800 collector, rack
environment unit, or ETH converter.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1.
2.
3.
Step 2 Add a PDU8000 (Modbus-RTU).
1.
Issue 05 (2019-09-16)
Choose System Info > Settings, enter the user name admin and password 000001, and
press
.
Tap Communication to set IP address assign to Automatic(DHCP) on the displayed
communication settings screen and the PDU8000 is discovered by ECC800
automatically and is connected to the ECC800.
Enter the PDU8000 home page, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
. In the password message dialog box displayed, click Confirm.
Tap Communication and check IP address assign to Manual. And set Serial port
baud rate to 9600, and Serial port address to 1 on the displayed communication
settings screen.
Figure 8-12 PDU8000 communication settings screen
Log in to the ECC800 WebUI as an administrator.