ECC800 Data Center Controller
User Manual
Step 2 Add an SVG.
1.
2.
3.
----End
Issue 04 (2021-10-09)
Figure 8-8 Setting SVG parameters
Log in to the ECC800-Pro WebUI as an administrator.
Add an SVG.
Table 8-7 Adding an SVG
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
for adding
Communicati
devices are
ons Port
displayed.
Device
Address
Click Test Connect to check whether the SVG connects to the ECC800-Pro
properly.
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU from the drop-down list box.
Select SVG-In-Power from the drop-down
list box.
Select ECC800 from the drop-down list
box.
Select COM2 from the drop-down list box.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the SVG based on the actual
situation.