How Can I Set And Add A Netcol5000-A011/A025/A035/A042/A050/A065 (Modbus-Tcp) - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Table 8-17 Adding an electricity meter
Path
Choose System
Settings > Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Step 3 Click Test Connect to check whether the electricity meter is properly connected to
the ECC800-Pro.
----End
8.7.18 How Can I Set and Add a NetCol5000-A011/A025/A035/
A042/A050/A065 (Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE_1 port on the
NetCol5000-A011/A025/A035/A042/A050/A065 main control board, and the other
end has been connected to the PoE port on the smart ETH gateway.
Context
The following describes how to set and add a NetCol5000-A042.
Procedure
Step 1 Set NetCol5000-A042 monitoring parameters.
1.
2.
Issue 04 (2021-10-09)
Parameter
Device attribute
Device Type
Connect To
Communications
Port
Device Address
If the connection succeeds, click Confirm. The device connection information
is displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to the
ECC800-Pro, whether the device and ECC800-Pro are running properly, and
whether the parameter settings are consistent with the device parameters.
Enter the NetCol5000-A042 home screen, tap Settings, choose the user name
admin, and enter the password 000001. After login, the settings screen of the
NetCol5000-A042 is displayed.
Choose Comm Settings > LAN IP Settings, set LAN IP assigning mode to
Automatic (DHCP), and click Submit.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Electricity Meter from the
drop-down list box.
Set this parameter based on the
connected device model.
Set this parameter based on the
connection position.
Set this parameter based on the
connected port.
Set this parameter based on the
communications address of the
electricity meter.
8 FAQ
325

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800

Table of Contents