6.7 Infrared Remote Control Module Control and
Management
In the FusionModule500 scenario, the automatic startup function is added for civil
smart cooling products. The infrared remote control module controls the startup
of smart cooling products through the monitoring module.

6.7.1 Connecting a Communications Cable

Procedure
Step 1 Connect the T/H sensor to the COM1 port on the ECC800-Pro using a network
cable.
Issue 04 (2021-10-09)
If the linkage logic in
implementation.
Table 6-46 Linkage logic 2
Input 1
Signal-Access
Actuator Group-
Collection-Door
Status
Register-
Register29
If the linkage logic in
open, refer to the following logic.
Table 6-47 Linkage logic 3
Input 1
Signal-Access
Actuator Group-
Collection-Door
Status
Register-
Register29
Copyright © Huawei Technologies Co., Ltd.
Table 6-45
uses a register, refer to the following
Operator
Input 2
OR
Signal-
FusionModule
Actuator Group-
Collection-Door
Status
AND
Constant-1
Table 6-46
is changed to Turn on lights 10s after door
Operator
Input 2
OR
Signal-
FusionModule
Actuator Group-
Collection-Door
Status
DELAY
Constant-10
6 Feature Description
Output
Register-
Register29
Signal-AC
Actuator Group-
Turn On Lights
Output
Register-
Register29
Signal-AC
Actuator Group-
Turn On Lights
231