ECC800 Data Center Controller
User Manual
Step 6 Configure NAT on the IVS1800.
(1) Configure the MU:
1.
2.
3.
(2) Configure the OMU:
1.
2.
(3) Configure the SMU:
1.
Issue 04 (2021-10-09)
Choose Maintenance > Unified Configuration, set Module Name to MU,
and click Search.
Click Edit in the record where the value of Parameter Name is MUNNatIP,
set the external IP address of the IVS1800, and click Save.
Figure 6-64 Setting the external IP address of the MU
Click Edit in the row where the value of Parameter Name is
NatRtspServerPort, and set the NAT port number of the MU. Ensure that the
setting is the same as the NAT mapped port number configured on the
firewall. Click Save.
NO TE
If no external IP address is mapped, retain the default value of NatRtspServerPort.
Set Module Name to OMU and click Search.
Click Edit in the row where the value of Parameter Name is OMUNNatIP
and set Value to the MUNNatIP address of the MU. Click Save.
Figure 6-65 Setting the external IP address of the OMU
Set Module Name to SMU and click Search.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
203