How To Set And Add A Ups5000-E - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
----End

5.3.3 How to Set and Add a UPS5000-E?

Prerequisites
Procedure
Step 1 Set the UPS5000-E monitoring parameters.
1.
2.
3.
Step 2 Add a UPS5000-E.
1.
Issue 07 (2020-03-16)
UPS2000-G and ECC800 are running properly, and whether the input parameters
are consistent with the UPS2000-G parameters.
The section describes how to add a UPS2000-G in a single UPS scenario. In a parallel UPS scenario, if
the common communications address of the Modbus card is added to the ECC800, all UPS2000-Gs can
be connected to the ECC800.
One end of the straight-through cable has been connected to the RS485 port on the
UPS5000-E monitoring module, and the other end has been connected to the COM port
on the ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the
view is consistent with the real object. If all devices have been added and powered on,
only the BLINK function of the ETH converter can be used to identify the mapping
between the UPS5000-E and ETH converter.
On the displayed screen after UPS5000-E startup, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
.
Tap Communication and set RS485 baud rate to 9600, and RS485 address to 1 on the
displayed communication settings screen.
Figure 5-2 UPS5000-E communication settings
Log in to the ECC800 WebUI as an administrator.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
89