Setting And Adding A Netcol5000-C030 (Over Modbus Rtu) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
2.
3.
4.
----End

5.3.6 Setting and Adding a NetCol5000-C030 (over Modbus RTU)

Procedure
Step 1 Set the NetCol5000-C030 monitoring parameters.
1.
2.
Step 2 Add a NetCol5000-C030.
1.
2.
3.
Table 5-5 Adding NetCol5000-C030 parameters
Parameter Name
Communications port
Device address
4.
Issue 06 (2020-01-02)
Choose Monitoring > Air Conditioner > NetCol5000-C0301.
0301 in NetCol5000-C0301 is variable and subject to change with the smart cooling product model and
connection sequence. 030 indicates the 30 kW model, and 1 indicates the smart cooling product
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters,
temperature and humidity parameters, and alarm parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
Enter the NetCol5000-C030 home page, click Settings, choose user name Admin and
enter password 000001. After login, the settings screen of the NetCol5000-C030 is
displayed.
Choose Settings > Comm Settings > Modbus Settings, choose Baud rate to 9600 and
set Comm address to 1 (range: 1–255).
The earlier version has Protocol setting on the screen. The actual screen prevails.
Log in to the ECC800 WebUI as an administrator.
Choose Home > Device Management.
Choose NetCol5000-C030 from the Device type drop-down list box, select Connect to
to ECC800. Then set device parameters, as listed in
The setting example indicates that the NetCol5000-C030 is connected to the COM1 port
on the ECC800. If the NetCol5000-C030 is connected to another port, set the number of
the connected port.
Setting
Select COM1 from the drop-down list box.
In this example, Device address is set to 1. During actual
configurations, set the device address for the NetCol5000-C030
based on the actual situation.
Click Connect Test to check whether the NetCol5000-C030 connects to the ECC800
properly.
If the NetCol5000-C030 connects to the ECC800 properly, click Add Device.