How Can I Set And Add An Ats - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
3.
----End

8.7.16 How Can I Set and Add an ATS?

Prerequisites
One end of the straight-through cable has been connected to the COM port on
the ATS, and the other end has been connected to the COM port on the ECC800-
Pro collector or ETH converter.
Context
The ATS (ABB) model is OMD800.
Procedure
Step 1 Set the ATS device address. On the ATS display panel, tap
Configuration > Modbus and set the device address.
Step 2 Add an ATS.
1.
Issue 04 (2021-10-09)
Path
Parameter
parameters
Connect To
for adding
devices are
Communicati
displayed.
ons Port
Device
Address
Click Test Connect to check whether the PDU2000 is properly connected to
the ECC800-Pro.
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
NO TE
● The ATS device address is 1 by default.
● The initial password is 0001 for the ATS display panel.
Log in to the ECC800-Pro WebUI as an administrator.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select ECC800 from the drop-down list
box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
PDU2000 is connected to the COM1 port on the
ECC800-Pro. If the PDU2000 is connected to
another port, select the number of the
connected port.
Enter the actual device address of the
PDU2000.