ECC800 Data Center Controller
User Manual
Table 6-11 Function commissioning
Check Method
Method 1: Attempt to open the door
using the configured authentication
mode.
Method 2: On the WebUI, choose
Monitoring > Aisle > Access Actuator
Group > Access Actuator n, and click
Controls to open the door remotely.
Step 4 Check the functions of the cabinet electronic lock or fingerprint lock.
Table 6-12 Function commissioning
Device
Cabinet
electronic lock
Issue 04 (2021-10-09)
Check Method
Method 1: Ensure that the
cabinet door is closed, and
attempt to open the door with
an IC card.
Method 2: On the WebUI,
choose Monitoring > Cabinet
> IT Cabinet n > E-LOCK n,
and click Controls to open the
door remotely.
Method 3: On the WebUI,
choose Monitoring > Cabinet
n > E-LOCK n,
> IT Cabinet
click Running Parameters,
and set Door open timeout.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Normal Connection Status
For method 1: The aisle door is opened
successfully.
For method 2: After you choose Query
> Access Event on the WebUI, you can
view the type of this access control
event.
Normal Connection Status
For method 1: Swipe an
authorized IC card, press the
lower part of the cabinet
electronic lock when the green
indicator blinks, and open the
cabinet electronic lock.
For method 2: After the
cabinet electrical lock is
remotely opened, press the
lower part of the cabinet
electronic lock after the green
indicator blinks, and open the
cabinet electronic lock. Choose
Query > Access Event on the
WebUI. You can view the type
of this access control event.
Method 3: If the time after the
electronic lock of the cabinet
is opened exceeds the value of
Door open timeout, a Door
open time-out alarm is
generated.