6.14.1.4 Setting the Transparent Transmission Function

Context
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > NMS Application > Transparent Transmission
Channel.
Step 3 Set COM2(Port:3212) to Enable and click Submit.
Figure 6-110 Transparent transmission channel
Table 6-64 Mapping between ECC800-Pro ports and port numbers
COM Port
Port Number
If a device is connected to a COM port on the UIM20A expansion module, the port
number is displayed on the WebUI after transparent transmission is enabled for
the COM port and the configuration is saved. For example, the port number of
COM1 on UIM1 is 3215 in
Issue 04 (2021-10-09)
Using the transparent transmission function, the NMS can directly manage
southbound components that are not monitored by the ECC800-Pro.
In this example, the COM2 port of the ECC800-Pro is used for transparent
transmission.
COM1
3211
NO TE
● An ECC800-Pro can connect to a maximum of four UIM20A expansion modules with the
transparent transmission function.
● A UIM20A expansion module provides a maximum of eight COM ports with the
transparent transmission function.
If the port is set for the first time, you are prompted to set an authentication
password. On the Set Authentication Password tab page, set
Authentication password and Confirm authentication password and click
Submit.
Copyright © Huawei Technologies Co., Ltd.
COM2
3212
Figure
6-110.
6 Feature Description
COM3
COM4
3213
3214