ECC800 Data Center Controller
User Manual
8.
Step 2 Set an alarm for card readers.
Set Logical level configuration for reader removed based on the fingerprint
reader configured for the access control system.
Step 3 Check the functions of the access control device and access actuator.
Issue 04 (2021-10-09)
Figure 6-7 Synchronizing access permissions
When Synchronization Status is Synchronization completed for the related
devices, close the Synchronize Access Permission page.
If the access control system uses a Card and password reader, choose
Monitoring > Aisle > Access Actuator Group > Access Actuator n on the
ECC800-Pro WebUI, click Running Parameters, and set Logical level
configuration for reader removed of the corresponding card reader to High
level alarm.
Table 6-10 Setting method
Cable Connection Scenario
The card reader with a keypad is
connected to WG_1 port on the
access actuator.
The card reader with a keypad is
connected to WG_2 port on the
access actuator.
If the access control system uses a Card, Card and fingerprint, or Card,
password and fingerprint reader, retain the default value Low level alarm
for Logical level configuration for reader removed.
Copyright © Huawei Technologies Co., Ltd.
Setting Method
Set Logical level configuration for
reader 1 removed to High level alarm.
Logical level configuration for reader 2
removed remains as Low level alarm.
Set Logical level configuration for
reader 2 removed to High level alarm.
Logical level configuration for reader 1
removed remains as Low level alarm.
6 Feature Description