How Can I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Rack Environment Unit) - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
Step 2 Check the monitoring functions of smoke sensor.
Table 8-25 Function check
Check Method
Simulate a
smoky
environment
under the smoke
sensor.
----End
8.7.29 How Can I Set and Add the Smoke Sensor (Connected
to the AI/DI Port on the Rack Environment Unit)?
If a smoke sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the network cable has been stripped, core wires 1, 5 and 8 have been
short-circuited, core wires 6 and 7 have been connected to the cable delivered
with the smoke sensor, and the other end of the network cable has been
connected to the AI/DI port on the rack environment unit.
Context
Issue 04 (2021-10-09)
The actual value prevails. Only the method of the parameter settings is
described.
NO TE
In this example, the smoke sensor is connected to the AI/DI_1 port on the skylight actuator.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Aisle > Skylight Actuator Group > Skylight Actuator
1 > Running Parameters > DI1 alarm level.
Set DI1 alarm level to Low voltage alarm or High voltage alarm, and click
Submit.
NO TE
– Set DI1 alarm level to Low voltage alarm if the smoke sensor is connected over
NO.
– Set DI1 alarm level to High voltage alarm if the smoke sensor is connected over
NC.
Normal Connection Status
DI1_smoke alarm is
displayed on the active
alarm page of the app or
WebUI.
If the sensor is prefabricated, only check its settings.
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
Press the reset button on the
smoke sensor to clear the
alarm.