ECC800 Data Center Controller
User Manual
Table 6-14 Function commissioning
Check Method
Attempt to open the door by pressing
the skylight button when the aisle
door is closed.
Step 3 Check functions of the atmosphere light.
Table 6-15 Function commissioning
Check Method
Press the atmosphere
light button.
Step 4 Check functions of the emergency button.
Table 6-16 Function commissioning
Check Method
Attempt to open the door
by pressing the emergency
button when the aisle
door is closed.
Step 5 Check functions of the magnetic lock.
Table 6-17 Function commissioning
Check Method
When the aisle door is
normally closed, check
whether there is a door
open alarm on the
ECC800-Pro.
----End
Issue 04 (2021-10-09)
Normal Connection Status
The atmosphere light is steady blue.
Normal Connection
Status
The aisle door is
opened successfully.
Normal Connection
Status
There is no door
open alarm on the
ECC800-Pro.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Normal Connection Status
The skylight can be opened manually.
Follow-up Procedure
You need to restore the
emergency button.
Troubleshooting
If a door open alarm is
reported when the door is
closed, relocate the
magnetic lock and magnet
to minimize the deviation
until the door open alarm
is cleared.