System Info - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

180 Parameters
No.
Name/Value
06.118
LSU start inhibit
status word
0000h...FFFFh
07

07 System info

07.03
Drive rating id
07.04
Firmware name
07.05
Firmware version
07.06
Loading package
name
07.07
Loading package
version
07.08
Bootloader version
07.11
Cpu usage
0...100%
07.13
PU logic version
number
Description
(Only visible when IGBT supply unit control activated by
95.20)
This word specifies the source of the inhibiting condition that
is preventing the supply unit from starting.
See also section
Control of a supply unit (LSU)
and parameter group
60 DDCS
This parameter is read-only.
Bit
Name
0
Not ready run
1
Ctrl location changed
2
SSW inhibit
3
Fault reset
4
Lost start enable
5
Lost run enable
6...8
Reserved
9
Charging overload
10...11 Reserved
12
Em Off2
13
Em Off3
14
Auto reset inhibit
15
Reserved
Start inhibit status word of supply unit.
Information on drive hardware, firmware and application
program.
All parameters in this group are read-only.
Type of the drive/inverter unit.
Firmware identification.
The format is AINFX, where X denotes the control unit type
(2 = BCU-x2, 6 = ZCU-12/14).
Version number of the firmware.
The format is A.BB.C.D, where A = major version, B = minor
version, C = patch (ie. firmware variant code), D = 0.
Name of the firmware loading package.
The format is AINLX, where X denotes the control unit type
(2 = BCU-x2, 6 = ZCU-12/14).
Version number of the firmware loading package. See
parameter 07.05.
Version number of the firmware bootloader.
Microprocessor load in percent.
Microprocessor load.
Version number of the power unit logic.
The value of FFFF indicates that the version numbers of
parallel-connected power units are different. See the drive
information on the control panel.
(page 77),
communication.
Def/FbEq16
-
1 = 1
-
-
-
-
-
-
-
1 = 1%
-

Hide quick links:

Advertisement