388 Parameters
No.
Name/Value
58.12
CRC errors
0...4294967295
58.14
Communication
loss action
No
Fault
Last speed
Speed ref safe
Fault always
Warning
58.15
Communication
loss mode
Any message
Cw / Ref1 / Ref2
Description
Displays a count of packets with a CRC error received by the
drive. An increasing count indicates interference on the bus.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Number of CRC errors.
Selects how the drive reacts to an EFB communication break.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
See also parameters
58.15 Communication loss mode
58.16 Communication loss
No action taken (monitoring disabled).
Drive trips on
6681 EFB comm
control is expected from the EFB (EFB selected as source of
start/stop/reference in the currently active control location), or
if supervision is forced using parameter
supervision
force.
Drive generates an
A7CE EFB comm loss
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the EFB, or if
supervision is forced using parameter
supervision
force.
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Drive generates an
A7CE EFB comm loss
the speed to the speed defined by parameter
safe
(or
28.41 Frequency ref safe
is being used). This only occurs if control is expected from the
EFB, or if supervision is forced using parameter
comm supervision force.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Drive trips on
6681 EFB comm
no control is expected from the EFB.
Drive generates an
A7CE EFB comm loss
occurs if control is expected from the EFB, or if supervision is
forced using parameter
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines which message types reset the timeout counter for
detecting an EFB communication loss.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
See also parameters
58.14 Communication loss action
58.16 Communication loss
Any message addressed to the drive resets the timeout.
A write of the control word or a reference from the fieldbus
resets the timeout.
time.
loss. This only occurs if
58.36 EFB comm
warning and
58.36 EFB comm
warning and sets
22.41 Speed ref
when frequency reference
loss. This occurs even though
warning. This only
58.36 EFB comm supervision
time.
Def/FbEq16
-
1 = 1
Fault
58.06
and
0
1
2
3
58.36 EFB
4
5
force.
Cw / Ref1 /
Ref2
58.06
and
1
2