174 Parameters
No.
Name/Value
06.39
Internal state
machine LSU CW
Bit
Name
0
ON/OFF
1
OFF 2
2
OFF 3
3
START
4...6
Reserved
7
RESET
8...11
Reserved
12
USER BIT 0 See parameter
13
USER BIT 1 See parameter
14
USER BIT 2 See parameter
15
USER BIT 3 See parameter
0000h...FFFFh
06.40
LSU CW user bit 0
selection
False
True
MCW user bit 0
MCW user bit 1
MCW user bit 2
MCW user bit 3
Other [bit]
06.41
LSU CW user bit 1
selection
False
True
MCW user bit 0
MCW user bit 1
MCW user bit 2
MCW user bit 3
Other [bit]
06.42
LSU CW user bit 2
selection
False
True
Description
(Only visible when supply unit control activated by 95.20)
Shows the control word sent to the supply unit from the INU-
LSU (inverter unit/supply unit) state machine.
This parameter is read-only.
Description
1 = Start charging
0 = Open main contactor (switch power off)
0 = Emergency stop (Off2)
0 = Emergency stop (Off3)
1 = Start modulating
0 = Stop modulating
0 - > 1 = Reset an active fault. A fresh start command is required after reset.
06.40 LSU CW user bit 0
06.41 LSU CW user bit 1
06.42 LSU CW user bit 2
06.43 LSU CW user bit 3
Supply unit control word.
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 12
of
06.39 Internal state machine LSU CW
0.
1.
Bit 12 of
06.01 Main control word
Bit 13 of
06.01 Main control word
Bit 14 of
06.01 Main control word
Bit 15 of
06.01 Main control word
Source selection (see
Terms and abbreviations
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 13
of
06.39 Internal state machine LSU CW
0.
1.
Bit 12 of
06.01 Main control word
Bit 13 of
06.01 Main control word
Bit 14 of
06.01 Main control word
Bit 15 of
06.01 Main control word
Source selection (see
Terms and abbreviations
(Only visible when supply unit control activated by 95.20)
Selects a binary source whose status is transmitted as bit 14
of
06.39 Internal state machine LSU CW
0.
1.
selection.
selection.
selection.
selection.
to the supply unit.
(see page 165).
(see page 165).
(see page 165).
(see page 165).
on page 148). -
to the supply unit.
(see page 165).
(see page 165).
(see page 165).
(see page 165).
on page 148). -
to the supply unit.
Def/FbEq16
-
1 = 1
MCW user bit
0
0
1
2
3
4
5
MCW user bit
1
0
1
2
3
4
5
MCW user bit
2
0
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents