604 Fault tracing
Code
Fault
(hex)
0005...0008 Internal error.
000E...0010 Internal error.
FF7E
Follower
FF81
FB A force trip
FF82
FB B force trip
Cause
0001 Maximum current limit too low.
0002 Maximum speed limit or
calculated field weakening
point too low.
0003 Maximum torque limit too low.
0004 Current measurement
calibration did not finish within
reasonable time.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
000C (Permanent magnet motors
only) First acceleration did not
finish within reasonable time.
000D (Permanent magnet motors
only) Second acceleration did
not finish within reasonable
time.
A follower drive has tripped.
A fault trip command has been
received through fieldbus
adapter A.
A fault trip command has been
received through fieldbus
adapter B.
What to do
Check settings of parameters
Motor nominal current
and
Maximum
current. Make sure that
30.17
> 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Check settings of parameters
30.11 Minimum speed
30.12 Maximum speed
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal
Make sure that
30.12
> (0.55 × 99.09) >
(0.50 × synchronous speed)
30.11
< 0, and
• supply voltage > (0.66 × 99.07).
Check settings of parameter
nominal
torque, and the torque limits in
group
30
Limits.
Make sure that the maximum torque limit
in force is greater than 100%.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
Check the fault information provided by
the PLC.
Check the fault information provided by
the PLC.
99.06
30.17
speed.
99.12 Motor