No.
Name/Value
35.24
Temperature 2 AI
source
Not selected
AI1 actual value
AI2 actual value
Other
35.30
FPTC configuration
word
Bit
Name
0
Module in slot 1
1
Disable slot 1 warning
2
Module in slot 2
3
Disable slot 2 warning
4
Module in slot 3
5
Disable slot 3 warning
6...15
Reserved
0000 0000b ...
0011 1111b
35.50
Motor ambient
temperature
-60 ... 100 °C or
-75 ... 212 °F
Description
Selects the input for parameter
selections
KTY84 analog
analog
I/O,
3 × Pt100 analog I/O
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
Source selection (see
Terms and abbreviations
Activates FPTC-xx thermistor protection modules installed on
the control unit of the drive. Using this word, it is also possible
to suppress the warnings (but not faults) from each module.
Description
1 = Yes: Module installed in slot 1.
1 = Yes: Warnings from the module in slot 1 suppressed.
1 = Yes: Module installed in slot 2.
1 = Yes: Warnings from the module in slot 2 suppressed.
1 = Yes: Module installed in slot 3.
1 = Yes: Warnings from the module in slot 3 suppressed.
FPTC-xx module configuration word.
Defines the ambient temperature of the motor for the motor
thermal protection model. The unit is selected by parameter
96.16 Unit
selection.
The motor thermal protection model estimates the motor
temperature on the basis of parameters 35.50...35.55. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING! The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
Ambient temperature.
35.21 Temperature 2
I/O,
1 × Pt100 analog
I/O,
and
Direct
temperature.
on page 148). -
Parameters 329
Def/FbEq16
source,
Not selected
2 × Pt100
0
1
2
0010 1010b
1 = 1
20 °C or
68 °F
1 = 1°