External Controller Interface - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

External controller interface

General
The drive can be connected to an external controller (such as the ABB AC 800M)
using either fiber optic or twisted-pair cable. The ACS880 is compatible with both the
ModuleBus and DriveBus connections. Note that some features of DriveBus (such as
BusManager) are not supported.
Topology
An example connection with either a ZCU-based or BCU-based drive using fiber optic
cables is shown below.
Drives with a
ZCU
module; drives with a
has a dedicated slot for the RDCO – an FDCO module can also be used with a BCU
control unit but it will reserve one of the three universal option module slots. Ring and
star configurations are also possible much in the same way as with the
master/follower link (see section
notable difference is that the external controller connects to channel CH0 on the
RDCO module instead of CH2. The channel on the FDCO communication module
can be freely selected.
Controller
T
R
T = Transmitter; R = Receiver
The external controller can also be wired to the D2D (RS-485) connector using
shielded, twisted-pair cable. The selection of the connection is made by parameter
60.51 DDCS controller comm
The transfer rate can be selected by parameter
Communication
The communication between the controller and the drive consists of data sets of three
16-bit words each. The controller sends a data set to the drive, which returns the next
data set to the controller.
control unit require an additional FDCO DDCS communication
BCU
control unit require an RDCO or FDCO module. The BCU
Master/follower functionality
ACS880
(ZCU) Control unit
T
port.
FDCO
R
60.56 DDCS controller baud
Program features 75
on page 68); the
ACS880
(BCU) Control unit
RDCO
CH0
T
R