ABB +N5600 Firmware Instructions page 605

Single drive
Table of Contents

Advertisement

Code
Fault
(hex)
FF8E
EFB force trip
D100
Cleaning max fault
D101
Overload
D102
Underload
Cause
A fault trip command has been
received through the
embedded fieldbus interface.
Maximum number of cleanings
in defined time frame has been
exceeded.
Overload supervision signal
exceeded the defined overload
supervision limit.
Underload supervision signal
exceeded the defined
underload supervision limit.
Fault tracing 605
What to do
Check the fault information provided by
the Modbus controller.
Check parameters
81.51 Cleaning max
event
to
81.53 Clean max period
445) for clean maximum protection
settings.
Check parameters
79.61 Overload
recovery speed
and
79.62 Overload
recovery speed
time.
Check parameters in group
protection
(page 429).
(page
79 Load