Name/Value
80.22
Additive voltage 2
-100.00...100.00 %
80.23
Additive voltage 3
-100.00...100.00 %
80.24
Additive voltage 4
-100.00...100.00 %
80.25
Additive voltage 5
-100.00...100.00 %
80.26
Additive voltage 6
-100.00...100.00 %
80.27
Additive voltage 7
-100.00...100.00 %
80.28
Additive voltage 8
-100.00...100.00 %
80.31
Validate tuning cmd
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other
80.32
Voltage tuner
source
NULL
AI1 scaled
AI2 scaled
FBA1 ref
FBA2 ref
Description
Defines voltage additive point 2 in the custom user U/F curve. 0.00
Additive voltage 2.
Defines voltage additive point 3 in the custom user U/F curve. 0.00
Additive voltage 3.
Defines voltage additive point 4 in the custom user U/F curve. 0.00
Additive voltage 4.
Defines voltage additive point 5 in the custom user U/F curve. 0.00
Additive voltage 5.
Defines voltage additive point 6 in the custom user U/F curve. 0.00
Additive voltage 6.
Defines voltage additive point 7 in the custom user U/F curve. 0.00
Additive voltage 7.
Defines voltage additive point 8 in the custom user U/F curve. 0.00
Additive voltage 8.
Defines the source for U/F curve tuning command.
This parameter provides possibility to manually tune the U/F
curve point settings while motor is running. When this
parameter is activated, the value received from parameter
80.32 Voltage tuner source
is converted to motor flux reference and applied instantly
instead of the value set in the u/f curve.
After tuning command is disabled, the actual motor speed
frequency is automatically written to the nearest frequency
point in the U/F curve and the voltage correction used at that
moment is then written to corresponding Additive voltage
parameter setting.
Validate tuning cmd is not selected.
Validate tuning cmd is selected.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
Defines the source for the voltage tuner signal.
This is used as additive voltage when parameter
Validate tuning cmd
is active.
Zero
See parameter
12.12 AI1 scaled value
See parameter
12.22 AI2 scaled value
See parameter
03.05 FB A reference 1
See parameter
03.06 FB A reference 2
is taken as the voltage additive. It
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on page 148). -
(see page 197).
(see page 199).
(page 156).
(page 156).
Parameters 439
Def/FbEq16
10 = 1%
10 = 1%
10 = 1%
10 = 1%
10 = 1%
10 = 1%
10 = 1%
Not selected
0
1
2
3
4
5
6
7
8
9
NULL
80.31
0
1
2
3
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents