ABB +N5600 Firmware Instructions page 203

Single drive
Table of Contents

Advertisement

No.
Name/Value
13.21
AO2 actual value
0.000 ... 22.000 mA Value of AO2.
13.22
AO2 source
13.26
AO2 filter time
0.000 ... 30.000 s
13.27
AO2 source min
-32768.0 ...
32767.0
Description
Displays the value of AO2 in mA.
This parameter is read-only.
Selects a signal to be connected to analog output AO2.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
For the selections, see parameter
Defines the filtering time constant for analog output AO2. See
parameter
13.16 AO1 filter
Filter time constant.
Defines the real minimum value of the signal (selected by
parameter
13.22 AO2
source) that corresponds to the
minimum required AO2 output value (defined by parameter
13.29 AO2 out at AO2 src
I
(mA)
AO2
13.30
13.29
13.27
Programming
13.27
as the maximum value and
minimum value inverts the output.
I
(mA)
AO2
13.30
13.29
13.28
Real signal value corresponding to minimum AO2 output
value.
13.12 AO1
source.
time.
min).
13.28
Signal (real)
selected by
13.22
13.28
13.27
Signal (real)
selected by
13.22
Parameters 203
Def/FbEq16
-
1000 = 1 mA
Motor current
0.100 s
1000 = 1 s
0.0
as the
1 = 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents