382 Parameters
No.
Name/Value
51.30
FBA A mapping file
ver
0...65535
51.31
D2FBA A comm
status
Not configured
Initializing
Time out
Configuration error
Off-line
On-line
Reset
51.32
FBA A comm SW
ver
51.33
FBA A appl SW ver
52

52 FBA A data in

52.01
FBA A data in1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
SW 32bit
Description
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
This parameter is read-only.
Mapping file revision.
Displays the status of the fieldbus adapter module
communication.
Adapter is not configured.
Adapter is initializing.
A timeout has occurred in the communication between the
adapter and the drive.
Adapter configuration error: mapping file not found in the file
system of the drive, or mapping file upload has failed more
than three times.
Fieldbus communication is off-line.
Fieldbus communication is on-line, or fieldbus adapter has
been configured not to detect a communication break. For
more information, see the documentation of the fieldbus
adapter.
Adapter is performing a hardware reset.
Displays the patch and build versions of the adapter module
firmware in format xxyy, where xx = patch version number, yy
= build version number.
Example: C802 = 200.02 (patch version 200, build version 2).
Patch and build versions of adapter module firmware.
Displays the major and minor versions of the adapter module
firmware in format xyy, where x = major revision number, yy =
minor revision number.
Example: 300 = 3.00 (major version 3, minor version 00).
Major and minor versions of adapter module firmware.
Selection of data to be transferred from drive to fieldbus
controller through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
52.01...52.12
the drive to the fieldbus controller through fieldbus adapter A.
None.
Control Word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Status Word (16 bits)
Actual value ACT1 (16 bits)
Actual value ACT2 (16 bits)
Control Word (32 bits)
Reference REF1 (32 bits)
Reference REF2 (32 bits)
Status Word (32 bits)
select data to be transferred from
Def/FbEq16
-
1 = 1
-
0
1
2
3
4
5
6
-
-
None
0
1
2
3
4
5
6
11
12
13
14