ABB +N5600 Firmware Instructions page 211

Single drive
Table of Contents

Advertisement

No.
Name/Value
14.27
DIO4 ON delay
0.00 ... 3000.00 s
14.27
AI1 scaled value
-32768.000 ...
32767.000
14.28
DIO4 OFF delay
0.00 ... 3000.00 s
14.28
AI1 force data
-22.000 ... 22.000
mA or V
14.29
AI1 HW switch
position
V
mA
14.30
AI1 unit selection
V
mA
14.31
RO status
0000b...1111b
14.31
AI1 filter gain
No filtering
125 us
Description
(Visible when
14.01 Module 1 type
Defines the activation delay for digital input/output DIO4. See
parameter
14.12 DIO1 ON
Activation delay for DIO4.
(Visible when
14.01 Module 1 type
Displays the value of analog input AI1 after scaling. See
parameter
14.35 AI1 scaled at AI1
This parameter is read-only.
Scaled value of analog input AI1.
(Visible when
14.01 Module 1 type
Defines the deactivation delay for digital input/output DIO4.
See parameter
14.12 DIO1 ON
Deactivation delay for DIO4.
(Visible when
14.01 Module 1 type
Forced value that can be used instead of the true reading of
the input. See parameter
Forced value of analog input AI1.
(Visible when
14.01 Module 1 type
Shows the position of the hardware current/voltage selector
on the I/O extension module.
Note: The setting of the current/voltage selector must match
the unit selection made in parameter
I/O module reboot either by cycling the power or through
parameter
96.08 Control board boot
any changes in the hardware settings.
Volts.
Milliamperes.
(Visible when
14.01 Module 1 type
Selects the unit for readings and settings related to analog
input AI1.
Note: This setting must match the corresponding hardware
setting on the I/O extension module (see the manual of the
I/O extension module). The hardware setting is shown by
parameter
14.29 AI1 HW switch
either by cycling the power or through parameter
Control board boot
is required to validate any changes in the
hardware settings.
Volts.
Milliamperes.
(Visible when
14.01 Module 1 type
Status of relay outputs on the I/O extension module.
Example: 0001b = RO1 is energized, RO2 is de-energized.
Status of relay outputs.
(Visible when
14.01 Module 1 type
Selects a hardware filtering time for AI1.
See also parameter
14.32 AI1 filter
No filtering.
125 microseconds.
=
FIO-01
or FIO-11)
delay.
=
FIO-11
or FAIO-01)
min.
= FIO-01)
delay.
=
FIO-11
or FAIO-01)
14.22 AI force
selection.
=
FIO-11
or FAIO-01)
14.30 AI1 unit
is required to validate
=
FIO-11
or FAIO-01)
position. I/O module reboot
=
FIO-01
or FDIO-01)
=
FIO-11
or FAIO-01)
time.
Parameters 211
Def/FbEq16
0.00 s
10 = 1 s
-
1 = 1
0.00 s
10 = 1 s
0.000 mA
1000 = 1 mA
or V
-
selection.
2
10
mA
96.08
2
10
-
1 = 1
1 ms
0
1